INSTALLATION INSTRUCTIONS
Diameter
PVC Sch 40
1 1/2--in.
38--mm
2--in.
51--mm
2 1/2--in.
64--mm
1067--mm
3--in.
76--mm
1067--mm
4--in.
102--mm
1219--mm
CAUTION
!
FURNACE RELIABILITY HAZARD
Failure to follow this caution may result in nuisance short
cycling, frozen vent termination, and/or no heat.
Slope the vent and combustion air piping downward towards
furnace at a minimum of 1/4--in. per linear ft. of pipe.
17. Slope the vent and combustion air piping and downward
towards furnace. A minimum slope of at least 1/4 in. per
linear ft.(1 in. per 4 ft.) with no sags between hangers is
required. See Caution Box below.
18. Complete the vent and combustion air pipe installation
by connecting to the concentric vent or by installing the
required termination elbows as shown in Figure 52 and
Figure 53, Alberta Figure 49 and Figure 51. For
ventilated
combustion
Figure 53, Alberta Figure 49 and Figure 51.
19. Use appropriate methods to seal openings where
combustion air pipe and vent pipe pass through roof or
sidewall.
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal
injury or death.
DO NOT use cement to join polypropylene venting
systems. Follow the polypropylene venting system
manufacturer's instructions for installing polypropylene
venting systems.
Optional Installation of the Vent Pipe
NOTE:
DO
NOT
USE
POLYPROPYLENE VENTING SYSTEMS.
This option provides a disconnect point for the vent pipe. The
vent pipe must be cemented to the plastic vent pipe adapter to
maintain a sealed vestibule. See Figure 46 and Figure 47
1. Insert a length of vent pipe through the casing into the
outlet of the vent elbow.
2. Slide the plastic vent pipe adapter over the length of the
vent pipe down to the furnace casing. Mark the pipe
where it is flush with the outlet of the adapter.
52
Hanger Spacing
SDR 21 & 26
3--ft.
2 1/2--ft.
914--mm
762--mm
3--ft.
3--ft.
914--mm
914--mm
3 1/2--ft.
3--ft.
914--mm
3 1/2--ft.
3--ft.
914--mm
4--ft.
3 1/2--ft.
1067--mm
air
terminations,
refer
THIS
TECHNIQUE
Specifications subject to change without notice.
Material
ABS
3--ft.
914--mm
3--ft.
914--mm
3 1/2--ft.
1067--mm
3 1/2--ft.
1067--mm
4--ft.
1219--mm
3. Remove the pipe from the furnace and the adapter and
cut off any excess pipe.
4. Clean and prime the end of the pipe that is flush with the
vent adapter with a primer that is appropriate for the type
of pipe being used.
5. Re--insert the pipe through the casing into the vent
elbow.
6. Tighten the clamp around the outlet of the vent elbow.
Torque the clamp to 15 lb--in.
7. Apply cement to the end of the pipe and to the inside of
the plastic vent adapter.
8. Slide the adapter over the vent pipe and align the screw
holes in the adapter with the dimples in the furnace
casing.
9. Pilot drill 1/8--in. screw holes for the adapter in the casing
and secure the adapter to the furnace with sheet metal
screws.
10. Loosen the clamps on the rubber vent coupling.
to
11. Slide the end of the coupling with notches in it over the
standoffs in the vent pipe adapter.
12. Tighten the clamp of the coupling over the vent pipe
adapter. Torque the lower clamp around the vent pipe
adapter to 15 lb--in.
13. Pilot drill a 1/8--in. hole in the combustion air pipe
adapter.
14. Complete the vent and combustion air pipe as shown in
"Install the Vent and Combustion Air Pipe"
FOR POLYPROPYLENE VENTING SYSTEMS
When using polypropylene venting systems, all venting
materials used, including the vent terminations, must
be from the same manufacturer.
FOR
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal
injury or death.
DO NOT use cement to join polypropylene venting
systems. Follow the polypropylene venting system
manufacturer's instructions for installing polypropylene
venting systems.
Gas Furnace: N9MSB
CPVC
Polypropylene
3--ft.
3.25--ft.
914--mm
1000 mm
3--ft.
3.25--ft.
914--mm
1000 mm
3 1/2--ft.
3.25--ft.
1067--mm
1000 mm
3 1/2--ft.
3.25--ft.
1067--mm
1000 mm
4--ft.
3.25--ft.
1219--mm
1000 mm
NOTICE
WARNING
440 01 4104 07