Venting; Special Venting Requirements For Installations In Canada - International comfort products C Series Installation Instructions Manual

Single-stage, psc blower motor 35” tall, high efficiency condensing gas furnace
Table of Contents

Advertisement

INSTALLATION INSTRUCTIONS
Figure 44
Example of Single Stage Furnace Control for PSC Blower Motor
115- -VAC (L2) NEUTRAL

VENTING

NOTE: Planning for the venting system should be done in
conjunction with planning for the ductwork, drainage, and
furnace accessories, such as air cleaners and humidifiers.
Begin assembling the venting system AFTER the furnace is set
in place in the required orientation.
Venting for this furnace shall follow all Local codes for category
IV venting systems. This furnace is CSA approved for venting
with PVC/ABS DWV venting systems. This furnace is also CSA
approved
for
venting
the
polyproplylene venting systems.
NOTE:
THESE
INSTRUCTIONS DO
DETAILED
INSTALLATION
POLYPROPYLENE
VENTING
polyproplylene venting system manufacturer's installation
instructions for the polyproplylene venting system installation.
NOTE: When using polypropylene venting systems, all venting
materials used, including the vent terminations, must be from
the same manufacturer.
Special Venting Requirements for Installations
in Canada
Installation in Canada must conform to the requirements of
CAN/CSA B149 code. Vent systems must be composed of
pipe, fittings, cements, and primers listed to ULC S636. The
special vent fittings, accessory concentric vent termination kits,
and accessory external drain trap available from the
manufacturer have been certified to ULC S636 for use with
those Royal Pipe and IPEX PVC vent components which have
been certified to this standard.
cement must be of the same manufacturer as the vent system
– GVS-65 Primer (Purple) for Royal Pipe or IPEX System 636,
PVC/CPVC Primer, Purple Violet for Flue Gas Venting and
GVS-65 PVC Solvent Cement for Royal Pipe or IPEX System
636
t, PVC Cement for Flue Gas Venting, rated Class IIA, 65
(1)
deg C. must be used with this venting system - do not mix
primers and cements from one manufacturer with a vent
440 01 4104 07
J2 JUMPER
OFF- -DELAY
24- -V THERMOSTAT
TERMINALS
24VAC
3- -AMP FUSE
COM/BLUE
24VAC/RED
LED OPERATION &
DIAGNOSTIC LIGHT
CONNECTIONS
SPARE1
SPARE2
SPARE1
BLOWER SPEED
SPARE2
SELECTION TERMINALS
SPARE3
M&G
DuraVentr
PolyPror
NOT CONTAIN
INSTRUCTIONS
FOR
SYSTEMS. Refer to
In Canada, the primer and
Specifications subject to change without notice.
HEAT
COMPONENT TEST
TERMINAL
HUMIDIFIER TERMINAL
(24- -VAC 0.5 AMP MAX)
HUM
TRANSFORMER 24- -VAC
CONNECTIONS
P1 - - LOW VOLTAGE MAIN
HARNESS CONNECTOR
EAC 1 AMP
1 - - AMP@115VAC
XFMR
SPARE3
HUM
115 VAC
(L1) LINE
VOLTAGE
HUMIDIFIER
CONNECTION
TERMINAL
115- -VAC
system
from
a
manufacturer's instructions in the use of primer and cement
and never use primer or cement beyond its expiration date.
The safe operation, as defined by ULC S636, of the vent
system is based on following these installation instructions, the
vent system manufacturer's installation instructions, and proper
use of primer and cement. All fire stop and roof flashing used
with this system must be UL listed material. Acceptability under
Canadian standard CAN/CSA B149 is dependent upon full
compliance with all installation instructions.
standard, it is recommended that the vent system be checked
once a year by qualified service personnel.
The authority having jurisdiction (gas inspection authority,
municipal building department, fire department, etc) should be
the
consulted before installation to determine the need to obtain a
permit.
*IPEX System 636™ is a trademark of IPEX Inc.
Consignes spéciales pour l'installation de
ventilation au Canada
L'installation faite au Canada doit se conformer aux exigences
du code CAN/CSA B149. Ce systême de ventillation doit se
composer de tuyaux, raccords, ciments et apprêts conformes
au ULC S636.
La tuyauterie de ventilation des gaz, ses
accessoires, le
terminal concentrique mural ainsi que
l'ensemble du drain de condensation extérieur fourni par le
fabricant de cette fournaise ont été certifiés ULC S636 pour
l'application des composantes Royal Pipe, IPEX PVC qui sont
certifiées à ce standard.
doivent être du même fabricant que le système d'évacuation.
L'apprêt GVS-65 (Purple) et le ciment-solvant GVS-65 doivent
être utilisé avec les Royal Pipe. Système IPEX 636, apprêt
PVC/CPVC, Purple pour évacuation des gaz de combustion et
système IPEX 636(1)t, ciment PVC pour évacuation des gaz
de combustion, coté classe IIA, 65 deg C. doivent être utilisés
avec le système d'évacuation IPEX 636 – Ne pas combiner l
Gas Furnace: N9MSB
P2
IND
HSI
P2- -HOT SURFACE IGNITOR (HSI) & INDUCER
MOTOR (IND) CONNECTOR
different
manufacturer.
Au Canada, l'apprêt et le ciment
L13F013
Follow
the
Under this
37

Advertisement