INSTALLATION INSTRUCTIONS
Size the Vent and Combustion Air Pipes
General
Vent or Combustion Air
Pipe Diameters
1 1/2−in.
2−in.
2 1/2−in.
3−in.
4−in.
Note: Optional accessory 2−pipe termination brackets are
sized for 2−in. and 3−in. Pipe. If a termination bracket is
required for a 4−in. termination, field fabricate the necessary
brackets and clamps.
Furnace combustion air and vent pipe connections are sized
for 2-in. (50 mm ND) PVC/ABS DWV pipe. The combustion air
and
vent
pipe
connections
polypropylene venting systems with outside diameters of
approximately 60 mm (2−3/8 inches). Any pipe diameter
change should be made outside furnace casing in vertical pipe.
Any change in diameter to the pipe must be made as close to
the furnace as reasonably possible.
The Maximum Vent Length for the vent pipe and combustion air
pipe (when used) equals the Maximum Equivalent Vent Length
(MEVL) in Table 14 or Table 16, minus the number of fittings
multiplied by the deduction for each type of fitting used from
Table 15.
NOTICE
OPTIONAL CONFIGURATION FOR COMBUSTION
AIR INLET PIPE
In applications where there is a risk of excessive mois-
ture entering the combustion air inlet pipe, a moisture
trap may be added to the inlet pipe to help prevent
moisture from entering the furnace from the combus-
tion air inlet pipe. See Figure 49.
When sizing venting systems, the equivalent length of
the optional moisture trap (15 feet/5 M) must be taken
into account
Optional Combustion Air Inlet
Moisture Trap
As an option to prevent moisture from trickling into the furnace
vestibule, a trap can be installed in the intake air pipe near the
furnace. Connecting a drain line to the trap is optional as trace
amounts of moisture will evaporate into the intake air stream. If
the combustion air inlet is located near a moisture exhaust
duct, or there are other concerns of excessive moisture being
drawn into the combustion air inlet, it is encouraged to connect
a drain line to the trap.
The trap can be constructed from a running tee of the same
diameter of the intake air pipe with EITHER a removable cap
attached to a 6-inch long pipe connected to the tee or the
External vent Trap Kit to help prevent contaminants from
entering the furnace. See Figure 49.
The External Vent Trap Kit accessory may be used as a trap for
the combustion air inlet pipe if a large amount of moisture must
be removed. The drain line may be connected to the same
drain as the furnace condensate and the evaporator coil
condensate line ONLY if the inlet air trap drain and the
evaporator coil drain empty into an open segment of pipe
above the drain, See Figure 12. When using the External Vent
42
Approved 2−pipe
termination fittings
2−in.
3−in.
4−in.
X
N/A
N/A
X
N/A
N/A
N/A
X
N/A
N/A
X
N/A
N/A
X
X
also
accommodate
60mm
Specifications subject to change without notice.
Trap Kit, refer to those instructions for proper drain
connections.
The tee may also be connected to the intake air pipe on the
side of the casing. See Figure 49.
In any configuration, it will be necessary to add the equivalent
length of the tee (15 feet/5 M) to the Total Equivalent Vent
Length of the venting system.
NOTICE
ADDITIONAL INFORMATION FOR POLYPROPYL-
ENE VENTING SYSTEMS
Polypropylene venting systems include flexible vent
pipe. These flexible vent pipes have a different equi-
valent vent length than straight sections of PVC/ABS
DWV vent pipe. Be sure to make the appropriate de-
ductions from the Maximum Equivalent Vent Length
(MEVL), or additions to the Total Equivalent Vent
Length (TEVL), when applying flexible vent pipes in
polypropylene venting systems. See the polypropylene
vent system manufacturer's installation instructions for
details.
When using metric-sized venting systems, use these
equivalencies for obtaining the proper MEVL from the
Tables:
Use 2" Vent Tables for 60mm (o.d.) vent systems
Use 3" Vent Tables for 80mm (o.d.) vent systems
Use 4" Vent Tables for 100mm (o.d.) vent systems
The measured length of pipe used in a single or 2−pipe
termination is included in the total vent length. Include
deductions from the Maximum Equivalent Vent Length (MEVL)
contained in the Venting Tables for elbows and flexible vent
pipe. Factory accessory concentric vent terminations, or pipe
lengths and elbows used for "standard" vent terminations (see
vent termination figures associated with Table 14) do not
require a deduction from the Maximum Equivalent Vent Length.
Include a deduction for a Tee when used for Alberta and
Saskatchewan terminations.
NOTE: Polypropylene venting systems MAY require additional
deductions from the MEVL, or additions to the TEVL, for vent
terminations and flexible pipe sections. See the polypropylene
venting system manufacturer's instructions for details on
equivalent lengths of vent terminations and flexible vent pipes,
and for calculating total vent lengths.
To calculate the Total Equivalent Vent Length (TEVL) of the
venting system:
1. Measure the individual distance from the furnace to the
termination for each pipe.
2. Count the number of elbows for each pipe.
3. For each pipe, multiply the number of elbows by the
equivalent length for the type of elbow used. Record the
equivalent length of all the elbows for each pipe.
4. If a Tee is used on the termination (Alberta and
Saskatchewan, when required), record the equivalent
length of the Tee used.
5. Calculate Total Equivalent Vent Length by adding the
equivalent lengths of the fittings to the lengths of the
individual vent and combustion air pipes.
6. When using polypropylene venting systems with flexible
vent pipes, perform adjustments for the equivalent length
of the flexible vent pipe to the calculated total equivalent
venting system length. See the polypropylene vent
system manufacturer's instructions for details.
7. Select a diameter of vent pipe from Table 14 and
Table 16 and note the Maximum Equivalent Vent Length
(MEVL) shown for that application for that specific
Gas Furnace: N9MSB
440 01 4102 01