4.3

Basic terminology

4.3.1

Redundancy/single-channel and two-channel

Redundancy
With redundancy, more than one component is implemented for the same function, so a faulty
function of a component is performed instead by the other component(s).
A redundant configuration reduces the probability of a function failing due to a single defective
component. This requirement is essential for achieving SILCL 3 in accordance with IEC 62061,
SIL 3 in accordance with IEC 61508 and PL e (Cat. 4) in accordance with ISO 13849-1 (also
necessary for SIL 2 / PL d under certain circumstances).
The simplest form of redundancy is two-channel redundancy.
If a circuit fails, two-channel redundancy or appropriate wiring ensures that the safety function
is maintained.
In a redundant system configuration, the subsystems for detecting and reacting must also be
implemented with two-channel redundancy.
Note
All SIRIUS Safety devices that comply with SILCL 3 in accordance with IEC 62061, SIL 3 in
accordance with IEC 61508 and PL e (Cat. 4) in accordance with DIN EN ISO 13849-1 are
redundantly configured with regard to the internal logic as well as with regard to the output
circuits.
Figure 4-1
SIRIUS 3SK1 Safety Relays and 3RQ1 Positively-Driven Coupling Relays
Equipment Manual, 05/2021, A5E02526190021A/RS-AE/005
Single-channel sensor connection
Safety systems - General information
4.3 Basic terminology
43