3.3 Identify the frame <= SSR TASK
STEP 4
Use the procedure "Appendix A: Power775 BPC FSP Command Line Procedure" (included in Section 5 of this
document) to access the BPC FSP command line of the frame with the Disk Enclosure needing its rails replaced.
STEP 5
Blink the Enclosure Identify LEDs of the DE with the FRU needing replacement by using the following command
from the BPC Command Line:
This is the command syntax:
bpccmd –c 27<blank>0000<cage ID><FRU ID><LED blink state 00=off, 02=blink>
Type in the following, inserting the correct Cage ID DE chassis location:
bpccmd –c 27110000xx0102
The correct return code is 001100. If you do not receive this, contact the next level of support.
Below is an example assuming Cage ID=0f
Power775 Disk Enclosure Rail Service Procedure
<blank>
= "11"
<cage ID>
= see Figure 5
<FRU ID>
= "01" for the DE Identify LED.
<LED state>
= "02" for this step
Where "xx" is the Cage ID of the DE you are servicing.
This field will be 05,07,09,0B,0D, or 0F (see Figure 5).