Installation

Selection of the best location

Indoor unit
Install the air conditioner in the location that satisfies the fol-
lowing conditions.
• The place shall easily bear a load exceeding four times the
indoor unit's weight.
• The place shall be able to inspect the unit as the figure.
• The place where the unit shall be leveled.
• The place shall easily connect with the outdoor unit.
• The place where the unit is not affected by an electrical
noise.
• The place where air circulation in the room will be good.
• There should not be any heat source or steam near the
unit
Confirm the positional relationship between the unit and
suspension bolts.
• Installation the ceiling opening to clean the filter or service
under the product.
Capacity (kBtu/h)
5/7/9
12/15/18
21/24
(Unit: mm)
A
B
600
800
600
1 000
600
1 200
Top view
Inspection hole
(Unit: mm)
(600 x 600)
600
Side view
(unit: mm)
• Suitable dimension "H" is necessary to get a slope
to drain as shown in the figure
B(Min)
A(Min)
Service Space
Installation Manual 7
Installation
Control box
Air outlet
600
Air outlet
H=20 or more
Ceiling
A
B