OPERATING PROCEDURE
12. Removing the compressor (MC)
(1) Remove the service panel. (See Photo 2)
(2) Remove the top panel. (See Photo 1)
(3) Remove the front panel. (See Photo 1)
(4) Remove the back panel. (See Photo 1)
(5) Remove the electrical parts box. (See Photo 5)
(6) Remove the thermistor <Discharge> (TH4) and thermistor
<Shell> (TH32). (See Photo 8)
(7) Remove 3 separator fixing screws (4 × 10) and remove
the separator.
(8) Recover refrigerant.
(9) Remove 3 compressor fixing nuts by using a spanner or a
adjustable wrench.
(10) Remove the welded pipe of motor for compressor inlet
and outlet.
Note: Recover refrigerant without spreading it in the air.
13. Removing the power receiver
(1) Remove the service panel. (See Photo 2)
(2) Remove the top panel. (See Photo 1)
(3) Remove the front panel. (See Photo 1)
(4) Remove the back panel. (See Photo 1)
(5) Remove the electrical parts box. (See Photo 5)
(6) Recover refrigerant.
(7) Remove 4 welded pipes of power receiver inlet and outlet.
(8) Remove 2 receiver leg fixing screws (4 × 10).
(9) Remove the power receiver together with the receiver leg.
Note: Recover refrigerant without spreading it in the air.
Photo 13
Compressor
(MC)
Separator
Separator
fixing screw
Compressor
fixing nut
Photo 14
Outlet
Receiver leg
fixing screw
120
PHOTOS
Valve bed
Inlet
Power
receiver
Receiver leg
Power
receiver

Hide quick links: