Siemens GEAFOL Operating Instructions Manual page 22

Cast-resin transformer
Table of Contents

Advertisement

GEAFOL- / CARECO-Cast-resin Transformer/ Operating Instructions
Potential faults
Faults
Transformer too hot,
Warning / alarm message
from the temperature
sensors of coils
Transformer too hot,
Warning / alarm message
from the temperature
sensors of core
Short circuit (triggering a
monitoring unit)
Traces of soot on the
transformer (Tracking)
Crack / chipped material
on high voltage coil mit
soot
Smell
Unusual noises
Table 9-2
Potential causes
Permanent overload
Screw connections on live parts
untighten
Bad ventilation, ambient tempera-
ture too high
Sensor defect
Permanent overvoltage
Inrush current too high
Dirt
Humidity too high
Dirt
Screw connections on live parts
untighten
Short circuit in coil
Evaporation after commissioning
Dirt in the coils or on the core
High voltage too high
Vibration of the housing,
Test steps / Remedy
Check load / load distribution,
reduce load if necessary
Tighten Screw connections on energized ter-
minals, torque values see chap. 6, table 6.2
Check the ventilation ducts on the housing,
fan and cooler, replace defective component if
necessary
Check the function of the relevant sensor,
if necessary, replace the sensor
Check voltage, reduce voltage if necessary
Adjust inrush current
Clean the transformer, see chap. 8.
Check ventilation, remove water, clear water
drainage,
Clean the transformer, see chap. 8, check ven-
tilation
Check screw connections, see chap. 8.
Call customer service - Do not switch the
transformer on again!
No action - the odor disappears after a few
hours
Clean the transformer, see chap. 8.
Check voltages, if necessary reduce the volt-
age
Tigthen of loose components,
attach vibration damper if necessary
© 2021 Siemens Energy
Page 22