GFK-2573Z
If the surrounding air operating temperature of the PNC001 is greater than 40  C, SFP devices could
have operating temperatures over 70 °C (158 °F). Under these conditions, for your safety, do not
use bare hands to remove an SFP device from the SFP cage. Use protective gloves or a tool (needle-
nose pliers) to avoid handling the hot SFP device directly when removing the SFP device.
5. Configuring the PNC001 and its I/O Devices on a PROFINET network
PME is the primary tool used to configure an RX3i PROFINET network. In addition, certain parameters can be set from a
computer through the PNC001's Command Line Interface. For details on system planning and configuration, refer to
PACSystems RX3i PROFINET I/O Controller Manual, GFK-2571, Chapter 3.
CAUTION
Whenever an RX3i PNC001 is extracted from a powered RX3i backplane, it loses power
immediately which may result in data loss. Do not remove or insert the device while downloading
hardware configuration to the system.
When the PNC001 is plugged back into a powered backplane, the PNC001 restores data from the
internal non-volatile memory. If, however, the RX3i CPU has configuration data for the PROFINET
Controller, it re-delivers the data to the PNC001, superseding parameters previously stored in non-
volatile memory.

Release History

Version
Firmware
IC695PNC001-BDBD
3.16
IC695PNC001-BCBD
3.16
IC695PNC001-BCBD
2
3.15
IC695PNC001-BBBC
3.11
IC695PNC001-BBBB
3.10
IC695PNC001-BABB
3.10
IC695PNC001-BABA
3.00
IC695PNC001-AN
2.27
Date
Revision
Sep
Manufacturing update. No change to fit, form, or function.
2020
Aug
Resolved a Loss of Device in an MRP Ring after the PNC001-Bxxx is reset.
2020
Oct
Rebranded the PNC001 to Emerson, applied patches for VxWorks URGENT/11
2019
vulnerabilities, and made additional updates to enhance cyber security.
May
Resolves an issue sending COMMREQs to the IC695GCG001 Genius Communication
Gateway if its PROFINET Device ID is 128 or greater.
2019
Hardware change: slight housing dimension change to address issue of difficulty
Nov
installing module into a slot with another module already installed in the left
2018
adjacent slot.
Corrects these issues: PROFINET IO Not Scanned After Loss of Both Critical Ring
Oct
Ports, Addition of IO Module Causes IO Device to Disconnect, and Bumpless IO Using
Link Change Detection May Fail Using a PNC001-Bxxx as a MRM. Also includes
2018
updates to enhance cyber security.
Feb
Redesign hardware and firmware for component obsolescence, reduce power
requirements, and comply with EU RoHS.
2018
May
Adds support for the Genius Communication Gateway's (GCG001) Switch BSM and
Enable/Disable Outputs COMMREQs.
2017
Sep 2020
Comments
7