Daikin Altherma 3 H MT F Installation Manual page 36

Hide thumbs Also See for Altherma 3 H MT F:
Table of Contents

Advertisement

10 Technical data
Electrical connection diagram
For more details, please check the unit wiring.
POWER SUPPLY
Only for normal power supply installation
1
5 or 3 core
Unit power supply:
400 V or 230 V + earth
Only for preferential kWh rate power supply installation
1
5 or 3 core
Unit preferential kWh rate power supply:
400 V or 230 V + earth
Normal kWh rate power supply for indoor unit:
2 core
230 V
FIELD SUPPLY
2 core
2
Preferential kWh rate power supply contact
2×0.75
Signal
Only for LV Smart Grid
2
Smart Grid contact S10S
OPTIONAL PART
2
Only for HV Smart Grid
Smart Grid contact K1A
2 core
2x0.75
Smart Grid relais K1A
2 core
2x0.75
Smart Grid relais K2A
2 core
HV Smart Grid control supply: 230 V
FIELD SUPPLY
2 core
3
Safety thermostat Q4L
2x0.75
7
Backup heater power supply (6 kW):
4 or 3 core
230 V + earth
(F1B)
7
5 core
Backup heater power supply (6/9 kW):
400 V + earth
(F1B)
FIELD SUPPLY
Power limitation demand input 1
Power limitation demand input 2
Power limitation demand input 3
Power limitation demand input 4
OPTIONAL PART
Only for WLAN module
A20P: J2
communication
Only for Bizone mixing kit
A30P: ST6
communication
Installation manual
36
STANDARD PART
OUTDOOR UNIT
X1M: L1-L2-L3-N-earth
or L-N-earth
X1M: 1-2-3-earth
4 core
INDOOR UNIT
X1M: 1-2-3-earth
X2M: 5-6
X5M: 9-10
ext. heat source output
X10M: 1-2
X10M: 3-4
X5M: 13
3
X5M: 14
X5M: 13-14
NO valve: X2M: 21-28
NC valve: X2M: 21-29
X6M: L1-L2-L3 + earth
or L-N + earth
X6M: L1-L2-L3-N + earth
Only for *KRP1AHTA
2 core
A8P: X801M: 1-5
signal
2 core
A8P: X801M: 2-5
signal
2 core
A8P: X801M: 3-5
signal
2 core
A8P: X801M: 4-5
signal
External room thermostat / Heat pump convector
(main and/or additional zone)
4
main: X2M: 30-34-35
add: X2M: 30-34a-35a
A11P: X5: 4-5
5 core
4
A11P: X9: 1-2-3
main: X2M: 30-31-34-35
add: X2M: 30-31-34a-35a
3 core
4
A11P: X3: 2-3-4
main & add: X2M: 3-4
Notes:
- In case of signal cable: keep minimum distance to power cables >5 cm
A4P: Y1-YC
2 core
Alarm indication
X2M: 7-9
Alarm output
230 V
A4P: X1-X2
2 core
Ext. heat source (e.g. boiler)
Changeover to
signal
A4P: Y2-YC
2 core
Cooling/heating On/OFF output
X2M: 7-9
Cooling/heating
230 V
On/OFF output
2 core
Circulation pump for domestic hot water
X2M: 1-2
230 V
2-way valve
2 core
M2S for cooling mode
230 V
2 core
Electricity meter pulse input 1
X5M: 5-6
signal
Only for HV Smart Grid
Smartgrid contact K2A
Only for LV Smart Grid
Smartgrid contact S11S
2 core
Electricity meter pulse input 2
X5M: 3-4
signal
Smartgrid pulse meter
Only for KRCS01-1 or EKRSCA1
2 core
X5M: 7-8
External thermistor (indoor or outdoor)
signal
Only for *KRTW (wired room thermostat)
3 core for C/H operation
2 core for H only operation
A2P: X1M: C-com-H
signal
Only for *KRTR (wireless room thermostat)
5 core for C/H operation
4 core for H only operation
A15P: X1M: H-C-com
X2M: L-N
signal
Only for heat pump convector
main: X2M: 30-35
add: X2M: 30-35a
4 core
A3P
signal
Only for Human Comfort Interface
2 core
2×0.75
X5M: 11-12
A14P: P1-P2 user interface
communication
FIELD SUPPLY
Only for *KRP1HB*
5
5
5
6
6
OPTIONAL PART
OPTIONAL PART
Only for *KRTETS
2 core
(3m included)
R2T External sensor (floor or
A2P: X1M: 1-3
ambient)
signal
4D133016B
ETVH/X12S18+23EA6V+9W
Daikin Altherma 3 H MT F
4P634880-1 – 2021.03