The following diagram shows the functional concept of
jumper configurations for Danger Relay actuation for
the Quad Relay Module. Note: The jumper
configuration shown is not applicable to the Velomitor
Signal Input Relay Module. For more details refer to
schematics in the applicable monitor manuals.
CAUTION
The following information is
not applicable to the
Velomitor. Refer to the
3300/55 Maintenance
Manual for jumper
configuration of the
Velomitor Relay Module.
FUNCTION
Set Danger relays for normally energized operation
Set Danger relays for normally de- energized
operation
Section 14 - DANGER RELAY ACTUATION CIRCUITS
INSTALL
W4B,4F
W1,3B,4A,4E
JUMPER
REMOVE
W1,3B,4A,4E
W4B,4F
27