Pressure / Temperature Chart - York MILLENNIUM Manual

Remote control center for style f air-cooled screw chiller
Hide thumbs Also See for MILLENNIUM:
Table of Contents

Advertisement

Refrigeration Overview
This chart shows characteristics of Refrigerant R-22 (Monochlorodifluoromethane) when in the 'saturated' state.
Temperature (F)
0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
SUCTION
36
38
40
42
44
46
48
50
52
54
56
58
60
62
64
66
68
70
72
74
76
78
80
82
84
86
88
90
16

PRESSURE / TEMPERATURE CHART

Pressure (PSIG)
24.0
25.6
27.3
29.1
30.9
32.8
34.7
36.7
38.7
40.9
43.0
45.3
47.6
50.0
52.4
54.9
57.5
60.1
62.8
65.6
68.5
71.5
74.5
77.6
80.8
84.0
87.4
90.2
94.3
97.9
101.6
105.4
109.3
113.2
117.3
121.4
125.7
130.0
134.5
139.0
143.6
148.4
153.2
158.2
163.2
168.4
Temperature (F)
92
94
96
98
100
102
104
106
108
110
112
114
116
118
120
122
124
126
DISCHARGE
128
130
132
134
136
138
140
142
144
146
148
150
152
154
156
158
160
Borders mark typical operating ranges that can be expected
for suction and discharge pressures under moderate to full
load, 44°F setpoint, with ambient air temperatures between
90-100°F. This is only a guideline and readings beyond these
ranges will occur.
Vapor entering compressor should be superheated 12-15°F.
Liquid from condenser should be subcooled 12-15°F. Econo-
mizer heat exchanger will provide up to an additional 20-28°F
of sub-cooling when in operation.
Pressure (PSI
173.7
179.1
184.6
190.2
195.9
201.8
207.7
213.8
220.0
226.4
232.8
239.4
246.1
252.9
259.9
267.0
274.3
281.6
289.1
296.8
304.6
321.5
320.6
328.3
337.3
345.8
354.5
363.3
372.3
381.5
390.8
400.3
410.0
419.8
429.8
YORK INTERNATIONAL

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents