Diagnostics alarms
5.1 Status and error displays
Meaning of the LED displays
The tables below explain the meaning of the status and error displays.
LED RUN/ERROR
Table 5- 1
RUN/ERROR status and error displays
LED
RUN
ERROR
Off
Off
Flashes
Off
On
Off
Flashes
Flashes
30
Meaning
Voltage missing or too low at backplane bus.
Module is starting up.
Module is ready.
Hardware defective.
Digital input/output module DI 32x24VDC SNK/SRC/DQ 32x24VDC/0.3A SNK BA (6ES7523-1BP50-0AA0)
Remedy
Switch on the CPU and/or the system power
supply modules.
Verify that the U connectors are inserted.
Check whether too many modules are in-
serted.
---
Replace the module.