Flue Options; Concentric Vent Screw Placement - UTICA BOILERS MAC-150 Installation, Operation & Maintenance Manual

Condensing wall mounted gas boiler
Table of Contents

Advertisement

Available languages

Available languages

Concentric Vent Support
All venting must be supported every 3.28 ft (1.00 m) using steel strapping or equivalent.
A: steel strapping or equivalent
Note:
Ensure that the vent is sloped towards the boiler approximately 0.79 in for every 3.28 ft (2.00 cm for every 1.00 m).
For horizontal flues a minor deviation from the horizontal is allowable, provided it results in a downward slope towards the boiler.
For the vertical flue terminal assembly refer to the separate installation instructions supplied with the assembly.
Additional flue components are available as follows:
45° bend
1.64 ft / 0.50 m
90° bend
3.28 ft / 1.00 m
Under no circumstances must the flue length (including allowances for extra bends) exceed 32.80 ft / 10.00 metres.
• Install a flue elbow on the adapter at the top of the boiler. Set the elbow to the required orientation (rear, right or left).
• Measure the distance from the outside wall face to the elbow. This dimension will be known as 'X'.
• To dimension 'X' add "Y" + 2 in (50 mm). This is the total dimension of the vents.
• Taking the air vent, mark the above dimension Measure the length of waste material, and transfer the dimension to the flue.
• Remove the waste from both vents (flue and air vents). Ensure that the cut ends are square and free from burrs.
• Insert the flue into the intake air vent and pass them through the hole in the wall
NOTICE
• Check all measurements before cutting. Minimum clearance to combustible materials when using a concentric
vent system is zero.
• After installing vents make sure that there is no recirculation of combustion by using a regularly calibrated analyzer.
• Ensure a minimum downward slope of 0.79 in / 2.00 mm for every 3.28 ft / 1.00 m of the flue length toward the boiler
at least 2º.
• Ensure that the terminal is positioned with the slots to the bottom.

Flue Options

• The boiler can be fitted with flue systems as illustrated.
• The standard flue (horizontal termination) is suitable only for horizontal applications.
• Maximum permissible equivalent flue lengths are:
Concentric and vertical flue = 32.80 ft / 10.00 m
• Any additional "in line" bends in the flue system must be taken into consideration.
Equivalent Straight Length
45° bend
1.64 ft / 0.50 m
90° bend
3.28 ft / 1.00 m
• The illustrations below show examples of maximum equivalent lengths.
• Instructions for guidance and fittings are included in each kit.
A
19
240011317, Rev. F [03/31/2017]