LG LS243HLV3 Installation Manual page 29

Single zone extended piping wall mounted
Hide thumbs Also See for LS243HLV3:
Table of Contents

Advertisement

Pipe Sleeves at Penetrations
LG recommends that all pipe penetrations through walls, floors, and pipes buried underground be properly insulated and routed through an
appropriate wall sleeve of sufficient size to prevent compression of refrigerant pipe insulation and free movement of the pipe within the
sleeve. Use 4"+ curved sheet metal saddles between the bottom surface of the pipe and the bottom surface of the penetration.
Figure 30: Pipe Sleeve Options.
Diameter of penetrations must be determined by pipe diameter plus the thickness of the insulation.
Underground Refrigerant Piping
Refrigerant pipe installed underground must be routed inside a vapor tight protective
sleeve to prevent insulation deterioration and water infiltration. Refrigerant pipe in-
stalled inside underground casing must be continuous without any joints. Underground
refrigerant pipe must be located at a level below the frost line.
Table 16: Utility Conduit Sizes.
Liquid
Pipe
1
3/8 (2.0
)
1/2 (2.0
2,5
1/4 (1.0)
4
3
3/8 (1-1/8)
4
3
1/2 (1-1/2)
5
4
5/8 (1-5/8)
5
4
3/4 (1-3/4)
5
4
OD pipe diameter in inches; Values in parenthesis () indicate OD of pipe with insulation jacket.
1
Diameter of pipe with insulation. Thickness of pipe insulation is typical. Actual required thickness will
2
vary based on surrounding ambient conditions and must be calculated and specified by the design
engineer.
3
Insulation thickness (value in parenthesis) = 3/8 inch.
4
Insulation thickness (value in parenthesis) = 1 inch.
5
Insulation thickness (value in parenthesis) = 3/4 inch.
REFRIGERANT SYSTEM ENGINEERING
Vapor Pipe
1
)
5/8 (2-1/8
) 3/4 (2-1/4
2,5
2,5
4
4
4
4
4
5
5
5
5
5
5
5
5
5
5
©
Figure 31: Typical Arrangement of Refrigerant Pipe
and Cable(s) in a Utility Conduit.
)
2,5
Table 17: Heat Pump Unit Refrigerant Pipe Connections (All Flared
Type).
Model
LSU243HLV3, LSU303HLV3,
LSU363HLV3
Provide expansion joints in long pipe segments and place in an accessi-
ble conduit box for inspection. Use galvanized curved sheet metal sad-
dles at all mounting points. Pipe must be allowed to move freely linearly.
Vapor Line
Insulation Material
Liquid Line
Pipe Sleeve
Insulation
Material
Communication /
Connection (Power) Cable
Liquid Conn.
Vapor Conn.
(inches)
(inches)
3/8
5/8
29