E403 : Freezing Control Causes Comp. Down - Samsung AC200KNHPKH Service Manual

Hide thumbs Also See for AC200KNHPKH:
Table of Contents

Advertisement

4-3-13 E403 : Freezing control causes comp. down

Outdoor unit display
Criteria
Cause of problem
1.
How to check
The indoor FAN/MOTOR operates normally?
The indoor EEV operates normally?
The indoor heat Exchanger sensor displays the
temperature ok?
Check for clogging in the suction area of the
indoor machine.
4-22
E403
•All the operating indoor machines do not reach -4°C for more than five minutes
•Check if the indoor FAN/MOTOR operates normally.
•Check if the indoor EEV operates normally.
•Check the indoor heat Exchanger's IN/OUT sensor.
•Check for clogging in the suction area of the indoor machine.
Yes
Yes
Yes
No
Check the indoor fan.
No
Check the EEV.
No
Same as when checking other temp sensors.
Samsung Electronics

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac250knhpkhAc200kxapnhAc250kxapnh

Table of Contents