7.1 Refrigerant cycle diagram
tank 1500cc
NOTE :
• You need not add refrigerant if the piping length is 40m or less.
• If the length exceeds 41m, add 20g of refrigerant per 1 meter over.
• Connection of only one indoor unit is unavailable. Two or more indoor units should be connected.
7. REFRIGERANT CYCLE DIAGRAM
High Pressure switch
Outdoor unit
- 31 -
FILE NO. SVM-18051
DX220A2T-20L
∅2 -∅3 , 450Lx2
∅2 -∅3 , 550Lx1
∅2 -∅3 , 600Lx1
1.92kg (R32)