Installing the Switch Chassis
• Ensure that you are positioning the switch in a rack so that it takes in cold air from the cold aisle and
exhausts air to the hot aisle. If there is blue coloring on the fan modules, the switch is configured for
port-side exhaust airflow and you must position the module side of the switch in a cold aisle. If there is
burgundy coloring on the fan modules, the switch is configured for port-side intake airflow and you must
position the port side of the switch in a cold aisle.
• Ensure that the chassis can be adequately grounded. If the switch is not mounted in a grounded rack, we
recommend connecting the system ground on the chassis directly to an earth ground.
• Ensure that the site power meets the power requirements for the switch. If available, you can use an
uninterruptible power supply (UPS) to protect against power failures.
• Ensure that circuits are sized according to local and national codes. Typically, this often requires one or
both of the following:
Caut i o n
Avoid UPS types that use ferroresonant technology. These UPS types
can become unstable with the switch, which can have substantial
current draw fluctuations because of fluctuating data traffic patterns.
• AC power supplies typically require at least a 15-A or 20-A AC circuit, 100 to 240 VAC, and a
frequency of 50 to 60 Hz.
• HVAC/HVDC power supplies require the following:
• HVAC input voltage range of 100 to 277 VAC with a frequency of 50 to 60 Hz
• HVDC input voltage range of -240 to -380 VDC
Caut i o n
To prevent loss of input power, ensure the total maximum loads on
the circuits supplying power to the switch are within the current
ratings for the wiring and breakers.
Note
For AC input application, please refer to the statement below:
W a r n i n g
Statement 1005 Circuit Breaker
This product relies on the building's installation for short-circuit
(overcurrent) protection. Ensure that the protective devices is rated
not greater than 20A (North America), 16A (Europe), and 13A (UK).
Note
For DC input application, please refer to the statement below:
Cisco Nexus 93240YC-FX2 NX-OS Mode Switch Hardware Installation Guide
Installation Guidelines
17