Converting Horizontal Supply Air Configuration; Condensate Connections; Duct System - Bosch LV Series Installation And Maintenance Manual

Table of Contents

Advertisement

8 | Installation
If the unit is located in a crawl space, the
bottom of the unit must be at least 4" above
grade to prevent flooding of the electrical
parts due to heavy rains.
Converting Horizontal Supply Air
Configuration
The supply air location on LV Series Horizontal
units can be quickly field converted from end blow
to straight through or vice-versa. To convert the
supply air direction, follow the steps below:
1. If connected to power, shut off the unit and
disconnect switch or circuit breaker.
2. Unscrew and remove the blower access panel.
3. Disconnect the wires from the unit electrical
box to the blower motor. Note which speed
taps are wired for units with PSC or constant
torque motors.
4. Unscrew and carefully remove the blower
panel with the blower and motor attached. Be
careful not to damage the refrigerant coils or
any other internal unit components.
5. Remove the blower support brackets from the
bottom of the blower housing and relocate
them to the top of the blower housing.
6. Turn the blower panel 180 degrees so that the
blower support brackets are now at the
bottom of the blower.
7. Insert the blower panel with the blower and
motor into the desired location. Be careful not
to damage the refrigerant coils or any other
internal unit components. Screw the panel
into place.
8. Replace the wires between the blower motor
and electrical box. Make sure to connect wires
to the proper speed taps.
9. Replace the blower access panel.
10. Reconnect power to the unit.

Condensate Connections

A drain line must be connected to the heat pump
and pitched away from the unit a minimum of 1/8"
per foot to allow the condensate to flow away from
the unit.
This connection must be in conformance with local
plumbing codes. A trap must be installed in the
condensate line to insure free condensate flow.
(Heat Pumps are not internally trapped).
8 733 905 683 (2013/04)
A vertical air vent is sometimes required to avoid
air pockets.(See Figure #3).
The depth of the trap depends on the amount of
positive or negative pressure on the drain pan. A
second trap must not be included.
The horizontal unit should be pitched
approximately 1/4" towards the drain in both
directions, to facilitate condensate removal. (See
Figure #4)

Duct System

All LV Series models are provided with a return air
duct flange and supply air duct connections.
Refer to unit Dimensional Drawings for physical
dimensions of the collar and flange. (Pg#49)
A flexible connector is recommended for supply
and return air duct connections on metal duct
systems. All metal ducting should be insulated
with a minimum of one inch duct insulation to
avoid heat loss or gain and prevent condensate
from forming during the cooling operation.
Application of the unit to uninsulated duct work is
not recommended as the unit's performance will
be adversely affected.
Do not connect discharge ducts directly to
the blower outlet.
The factory filter rack should be left in place
on a free return system.
Subject to change without prior notice
LV Heat PumpSeries
Figure # 3 Condensate Drain
Figure # 4 Pitched Unit
LV Heat Pump Series

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents