About Advanced Operation - Bryant TSTATBBPS701 User's Information Manual

Programmable digital thermostat
Table of Contents

Advertisement

About Advanced Features & Operation
MEMORY BACKUP - In the event of a power loss, the
thermostat will retain the stored program settings without
external power or batteries.
2 STAGE OPERATION - The 2nd Stage of heat or cool is
turned on when (1) the 1st Stage has been on for a
minimum of two minutes, and (2) the temperature spread
from the setpoint is equal to or greater than: the setpoint
plus the deadband, plus 2 degrees.
Heating
2 degrees
1st Stage
2nd Stage
turn on
turn on
MINIMUM HEAT/COOL SETPOINT DIFFERENCE - The Heat
and Cool setpoints will not be allowed to come any closer
to each other than the value set in Advanced Setup step
# 7, on page 13. This minimum difference is enforced
during Auto changeover
PROGRAMMABLE FAN - If the Programmable Fan timer is
set to a value other than 0:00, the fan will run for the
preprogrammed amount of time,
The Programmable Fan timer will start the fan at the top
of each hour. The Programmable Fan may be active
even if the thermostat mode is Off. Steps 10 & 11
restrict the hours in which Programmable Fan may
operate. Step# 10, page 14 is the start time and step# 11
is the stop time. Setting the times to the same setting
in both steps 10 & 11 will allow Programmable Fan to
operate 24 hours a day.
Cooling
Dead
Dead
Band
Band
2 degrees
1st Stage
Heat
Cool
Setpoint
Setpoint
turn on
and Program On
operation.
page 13, step# 9.
Page 17
2nd Stage
turn on