Outdoor Unit Installation; Installing Outdoor Unit; Drain Work - Daikin RXS24LVJU Installation Manual

Hide thumbs Also See for RXS24LVJU:
Table of Contents

Advertisement

Installation Guidelines
• Where a wall or other obstacle is in the path of outdoor unit's inlet or outlet airflow, follow the installation guidelines below.
• For any of the below installation patterns, the wall height on the outlet side should be 47-1/4 inch (1200mm) or less.
Wall facing one side
More than
More than
3-15/16 (100)
13-3/4 (350)
47-1/4
(1200)
or less
Side view

Outdoor Unit Installation

1.

Installing outdoor unit

1) When installing the outdoor unit, refer to "Precautions for Selecting the Location" and the "Outdoor Unit Installation Drawings".
2) If drain work is necessary, follow the procedures below.
2.

Drain work

• Use drain plug for drainage.
• If the drain port is covered by a mounting base or floor surface, place additional foot bases of at least 3-15/16 inch
(100mm) in height under the outdoor unit's feet.
• In cold areas, do not use a drain socket (A), drain caps (B) and a drain hose with the outdoor unit.
(Otherwise, drain water may freeze, impairing heating performance.)
1) Insert drain receiver (C) onto drain socket (A) and drain cap (B) beyond 4
projections around drain socket and drain cap.
2) Insert drain socket and drain caps into their matching drain hole; Drain socket
(A) into drain hole I and drain caps (B) into drain hole II and III. After insertion,
turn them about 40° clockwise.
II
I
III
NOTE
Check that the drain receiver (C) is correctly engaged with the projections of the drain socket (A) and drain cap (B).
Otherwise, water leakage may result.
3) C onnect vinyl hose on the market (internal diameter of 1 inch (25mm)) to drain socket (A).
(If the hose is too long and hangs down, fix it carefully to prevent the kinks.)
4) Make sure that there is no water leakage from portion I, II, or III.
NOTE
If the drain holes of the outdoor unit are covered with the mounting bracket or the floor, raise the unit to provide the space of
more than 3-15/16 inch (100mm) under the leg of the outdoor unit.
English
Walls facing two sides
More than
13-3/4 (350)
More than
3-15/16 (100)
More than
1-15/16 (50)
Top view
(Be sure not to insert them into wrong drain
holes, or there causes water leakage.)
(View from bottom)
Projections
(4 points)
Walls facing three sides
More than
1-15/16 (50)
More than
1-15/16 (50)
(A) Drain socket
Projections
Projections
(4 points)
More than
3-15/16 (100)
More than
13-3/4 (350)
Top view
unit: inch (mm)
(B) Drain cap
Projections
(C) Drain receiver
5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents