Wiring Diagrams - Bryant T1--PAC Installation Instructions Manual

Legacy line-rnc programmable thermostats
Table of Contents

Advertisement

pressing UP and FAN buttons simultaneously or changing the
setpoint will override the timer for 1 cycle.
Minimum on Timer
Once the equipment has turned on, it will remain on for a
minimum of 3 minutes regardless of demand. However, the
equipment can turn off in less than 3 minutes if a change in
setpoint, or a change in mode occurs.
Staging Timer
If the thermostat is a heat pump model, it has 2- -stage heat
capability. In normal operation there is a 15- -minute delay between
the first and second stages of heat. The Y output will energize first,
then 15 minutes later, W is allowed to come on if the thermostat
determines it is not satisfying the demand.
However, if the heating demand is greater than 5_F/3_C, there will
be only a 30 second delay before bringing on W.
Auxiliary Heat Indicator
When operating a heat pump and either auxiliary heat or
emergency heat is active, a front mounted LCD indicates this
condition.
Error Messages
If the room temperature sensor fails, two dashes (- -- -) will appear in
the temperature display and all heating and cooling outputs will be
turned off. The thermostat must be replaced.
EQUIPMENT
CONFIGURATION
OPTION #1
AC, PC
HP , PH
RVS = C
HP , PH
RVS = H
Fig. 1 - - A/C Thermostat Typical Installation
E2010 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
THERMOSTAT
COOL
FACTORY
STAGE 1
CONFIGURATION
AC, HP
Y, G
HP
Y, G, O/B
HP

WIRING DIAGRAMS

If the internal non- -volatile memory fails, E4 will alternately flash
with the temperature on the display and all heating and cooling
outputs will be turned off. The thermostat must be replaced.
Step 5 — Check Thermostat Operation
Fan Operation
1. Press FAN button. This will start continuous fan operation.
FAN ON icon will turn on.
2. Press FAN button again. This will stop continuous fan oper-
ation. FAN ON icon will turn off.
Heating Operation
1. Press H/C button until HEAT is displayed.
2. Press UP button until LCD readout reads 3_F/2_C above
room temperature. Press UP and FAN buttons simultan-
eously to defeat timers. Heating system should begin to op-
erate immediately.
3. For HP thermostats only, press H/C button until EMHT
(emergency heat) appears. Press UP and FAN buttons sim-
ultaneously to defeat timers. Emergency heating (W is ON,
Y is OFF) should begin immediately.
Cooling Operation
1. Press H/C button until COOL is displayed.
2. Press DOWN button until LCD readout reads 3_/2_C be-
low room temperature. Press UP and FAN buttons simultan-
eously to defeat timers. Cooling system should begin to op-
erate immediately.
Table 1 shows the thermostat outputs for each available stage of
A07821
heating or cooling. It may be useful in checkout or
troubleshooting.
Table 1 – Outputs
HEAT
STAGE 1
W
Y, G
Y,G
Y, G, O/B
A06566
Fig. 2 - - HP Thermostat Typical Installation
Printed in U.S.A.
Edition Date: 02/10
4
HEAT
EM HEAT
STAGE 2
--- ---
--- ---
Y, G, W
W
Y, G, W, O/B
W
Catalog No. IIT1---PAC ---08
Replaces: IIT1--- PAC--- 07
A06567