Wiring Requirements; Thermostat Control Wire; Zone Sensor Wire; Shielded Twisted Pair Cable - Trane Odyssey Series Installation Manual

Split system air conditioners
Table of Contents

Advertisement

Wiring Requirements

Thermostat Control Wire

Table 1. Recommended thermostat control wire size

Zone Sensor Wire

Table 2. Zone sensor module wiring

Shielded Twisted Pair Cable

A shielded twisted pair cable is required for Symbio condenser installations where the indoor air
handler is variable speed supply fan (VFD) and/or electric heat. See Air Handler and Condenser
pairing information for more details regarding shield twisted pair cable installation requirements.
Trane Purple Wire is recommended when shielded twist pair cable is required (see the following
table).
Alternate shield twisted pair cable can be used if it conforms to the following physical
characteristics:
6
Wire Gauge
22
20
18
16
14
Distance from Unit to Control
0–150 feet (0–45.7 meters)
151–240 feet (46–73.1 meters)
Part Number
Cable, comlink cable with PVC jacket, 18/1 pr, stranded shield, 25PF plenum, 100 foot
CAB01568
Cable, comlink cable with PVC jacket, 18/1 pr, stranded shield, 25PF plenum, 1,000 foot
CAB01569
Twisted pair (two-conductor) plus shield
Characteristic impedance: 100 and 130 ohms
Distributed capacitance between conductors: < 100 pF/m
Distributed capacitance between conductor and shield: < 200 pF/m
Foil or braided shield is acceptable
Wire diameter: 22 to 18 AWG
Maximum Wire Length
30 feet
50 feet
75 feet
125 feet
200 feet
Recommended Wire Size
22 gauge (0.33 mm
20 gauge (0.5 mm
Description
length
length
2
)
)
2
SS-SVN016A-EN