Configure The Occuswitch Dali; Checks; Hold Timer; Assigning Luminaires To Dali Groups - Philips OccuSwitch DALI LRM2070 User Manual

Hide thumbs Also See for OccuSwitch DALI LRM2070:
Table of Contents

Advertisement

4.2

Configure the OccuSwitch DALI

4 .2 . 1

Checks

Make sure that the OccuSwitch DALI system has been
installed correctly, by checking the LEDs and luminaires
function .
4 .2 .2

Hold timer

The hold timer defines the time after which the lights will
be turned to the background light level, or be turned off .
1 Turn the potentiometer to the desired value .
As shown in the figure, the potentiometer range is not
linear, but divided in a number of possible settings .
4 .2 .3
groups
II
I/ II
BMS
PL
W/C
1
2
3
10% A
20% B
30% C
1 Press the DALI button to start the
4
5
6
40% D
50% E
60% F
7
8
9
assigning process .
70% G
on
0
o
min
The luminaires flash indicating that
group
the OccuSwitch DALI has received the
save
command . One by one all luminaires
con g
mode
O)))
will dim . When this process stops one
link?
mode?
test
100 h
luminaire starts to blink .
add
zone
%
A-G
on/o
0
power up background IR group
reset
2 Select the DALI group this luminaire
delay
pir
daylight RF channel
should be assigned to,
scene
1 = (Window), 2 = (Corridor),
3 = (Additional Presence) or
4= (Additional Absence) .
Directly after sending the group number
another luminaire starts to blink .
Repeat step 2 for all other luminaires .
When all luminaires are assigned to
a DALI group, all luminaires will blink
once, and the OccuSwitch DALI returns
to normal operation .
Assigning luminaires to DALI
D Notes
• At all actions, stay close to the OccuSwitch DALI and
point the remote control towards the sensor .
• The procedure above can be aborted at any moment
by pressing the DALI button again . Aborting the
assign process will reset all luminaires and/or
drivers to un-commissioned mode . See the tables
in sections 2 . 1 . 1 , 2 . 1 .2 and 2 . 1 .3 for the behavior of
OccuSwitch DALI Basic, Advanced or BMS when in
the un-commissioned mode .
• If the DALI group is not assigned correctly you can:
• Press the DALI button again to reset the system to
un-commissioned mode and start the re-program
the luminaires
or
• Reset the complete OccuSwitch DALI to factory
settings (see section 4 .3) .
4 .2 .4

Calibration of the required light level

The OccuSwitch DALI will already function quite well in
most applications since the factory settings are designed
for the common offices . However calibration is required
to reach optimal cost savings, and to be certain that the
minimal required light levels are met .
The OccuSwitch DALI should be calibrated after:
• The furniture is in placed in the room .
• Major changes have been made to the room or furniture
placement .
Before calibration
• Make certain you have the right tools (IRT9090 and a
lux meter)
• Make certain that the daylight contribution to the rooms
light level is less than 70% .
You can easily check this . The level you measure with
the lights switched off should be below 70% of the
required light level .
Closing the curtains or sun blinds can already take care
of this .
• Make certain that the amount of daylight is not
fluctuating during the measurement . A partly clouded
sky with fast moving clouds can hamper the right
measurements .
While this section describes several methods to calibrate
the system, it is recommended to use the IRT9090
extended IR programming tool for system calibration .
OccuSwitch DALI