OUTDOOR
COIL
Fig. 11 - - Cleaning Condenser Coil (Size 04- - 07 shown)
Fig. 12 - - Propping Up Top Panel
4. For Sizes 04- - 07: Remove screws securing coil to
compressor plate and compressor access panel.
5. For Sizes 08- - 09: Remove fastener holding coil sec-
tions together at return end of condenser coil. Care-
fully separate the outdoor coil section 3 to 4 in. from
the inner coil section. See Fig. 13.
Fig. 13 - - Separating Coil Sections
6. Use a water hose or other suitable equipment to flush
down between the 2 coil sections to remove dirt and
debris. Clean the outer surfaces with a stiff brush in
the normal manner.
7. Secure inner and outer coil rows together with a
8. Reposition the outer coil section and remove the coil
Totaline Environmentally Sound Coil Cleaner
Application Equipment
S 2
S Water rinse with low velocity spray nozzle
UNIT DAMAGE HAZARD
Failure to follow this caution may result in corrosion
C09219
and damage to the unit.
Harsh chemicals, household bleach or acid or basic
cleaners should not be used to clean outdoor or indoor
coils of any kind. These cleaners can be very difficult
to rinse out of the coil and can accelerate corrosion at
the fin/tube interface where dissimilar materials are in
contact. If there is dirt below the surface of the coil,
use the Totaline environmentally sound coil cleaner as
described above.
C08206
UNIT DAMAGE HAZARD
Failure to follow this caution may result in reduced
unit performance.
High velocity water from a pressure washer, garden
hose, or compressed air should never be used to clean
a coil. The force of the water or air jet will bend the
fin edges and increase airside pressure drop.
Totaline Environmentally Sound Coil Cleaner
Application Instructions
1. Proper eye protection such as safety glasses is recom-
2. Remove all surface loaded fibers and dirt with a vacu-
OUTDOOR
COIL
3. Thoroughly wet finned surfaces with clean water and
4. Mix Totaline environmentally sound coil cleaner in a
NOTE: Do NOT USE water in excess of 130°F (54°C), as
C09220
the enzymatic activity will be destroyed.
5. Thoroughly apply Totaline environmentally sound
6. Hold garden sprayer nozzle close to finned areas and
9
field- - supplied fastener.
corner post from between the top panel and center
post. Reinstall the coil corner post and replace all
screws.
1
/
gallon garden sprayer
2
CAUTION
!
CAUTION
!
mended during mixing and application.
um cleaner as described above.
a low velocity garden hose, being carefull not to bend
fins.
1
2
/
gallon garden spryer according to the instruc-
2
tions included with the cleaner. The optimum solution
temperature is 100°F (38°C).
coil cleaner solution to all coil surfaces including
finned area, tube sheets and coil headers.
apply cleaner with a vertical, up- - and- - down motion.