graph with the left side of the chart to determine that the
range configuration for the CO
ppm. The EconoMi$er IV controller will output the 6.7
volts from the CO
sensor to the actuator when the CO
2
concentration in the space is at 1100 ppm. The DCV
setpoint may be left at 2 volts since the CO
voltage will be ignored by the EconoMi$er IV controller
until it rises above the 3.6 volt setting of the minimum
position potentiometer.
Once the fully occupied damper position has been
determined, set the maximum damper demand control
ventilation potentiometer to this position. Do not set to the
maximum position as this can result in over-ventilation to
the space and potential high humidity levels.
CO
Sensor Configuration
2
The CO
sensor has preset standard voltage settings that
2
can be selected anytime after the sensor is powered up.
(See Table 23.)
Use setting 1 or 2 for Bryant equipment. (See Table 23.)
1. Press Clear and Mode buttons. Hold at least 5 seconds
until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to select the preset number.
(See Table 23.)
SETTING
EQUIPMENT
1
Interface w/Standard
2
Building Control System
3
4
5
Economizer
6
7
8
Health & Safety
Parking/Air Intakes/
9
Loading Docks
LEGEND: ppm — Parts Per Million
sensor should be 1800
2
2
sensor
2
Table 23 – CO2 Sensor Standard Settings
VENTILATION
OUTPUT
RATE
(cfm/Person)
Proportional
Any
Proportional
Any
Exponential
Any
Proportional
15
Proportional
20
Exponential
15
Exponential
20
Proportional
Proportional
4. Press Enter to lock in the selection.
5. Press Mode to exit and resume normal operation.
The custom settings of the CO
anytime after the sensor is energized. Follow the steps
below to change the non-standard settings:
1. Press Clear and Mode buttons. Hold at least 5 seconds
until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to toggle to the NONSTD
menu and press Enter.
4. Use the Up/Down button to toggle through each of
the nine variables, starting with Altitude, until the
desired setting is reached.
5. Press Mode to move through the variables.
6. Press Enter to lock in the selection, then press Mode
to continue to the next variable.
Dehumidification of Fresh Air with DCV (Demand
Controlled Ventilation) Control
If normal rooftop heating and cooling operation is not
adequate for the outdoor humidity level, an energy
recovery unit and/or a dehumidification option should be
considered.
CO
2
ANALOG
CONTROL RANGE
OUTPUT
(ppm)
0-10V
0-2000
4-20 mA
2-10V
0-2000
7-20 mA
0-10V
0-2000
4-20 mA
0-10V
0-1100
4-20 mA
0-10V
0- 900
4-20 mA
0-10V
0-1100
4-20 mA
0-10V
0- 900
4-20 mA
0-10V
0-9999
4-20 mA
0-10V
0-2000
4-20 mA
54
sensor can be changed
2
OPTIONAL
RELAY
RELAY SETPOINT
HYSTERESIS
(ppm)
(ppm)
1000
50
1000
50
1100
50
1100
50
900
50
1100
50
900
50
5000
500
700
50