American Water Heater 240HX3 Installation Manual And Owner's Manual page 19

On-demand water heater
Table of Contents

Advertisement

Determine type of ventilation
There are several types of ventilation that can be used. The various options are listed below. See also the illustra-
tions on the next page.
1. Direct to outdoors
2. Vertical ducts
3. Horizontal ducts-Single opening (not recommended; must be at least 100 in
fined spaces smaller than 50 ft
4. From a larger room inside the house (not recommended – refer to "Calculate the air volume of the room" above to
determine if the combined volume of the rooms may be adequate).
Determine minimum free area required for each vent opening
The size of the vent openings depends on the total BTU/h rating of all appliances in the space (use your calculation from "Be-
fore beginning") and the type of vent used. Table 1 provides the minimum free area for each vent opening depending on the
type of ventilation.
Calculate minimum size of vent openings and ducts
The vent cross-sectional area needed to provide the free area depends on the covering on the vent openings. Typical vents use
louvers or grilles to protect the opening. The louver or grill itself blocks some of the free area, so the opening may need to be
larger to meet the minimum free area requirements.
Use the following formula to calculate the required cross-sectional area:
Cross-sectional area = minimum free area required ÷ percent free area of covering (in decimals – e.g., 60 % = 0.6)
For example, an installation area that requires openings with 100 in
(865 cm
) openings if using metal louvers rated at 75% free area (100 in
2
If you do not know the % free area for your louver or grill, use the following values:
For wood louvers or grilles: 25%
For metal louvers or grilles: 75%
Follow these rules to ensure that vents and ducts provide adequate air flow:
Each vent opening must be no smaller than 100 in
Ducts must have the same cross-sectional area as free area of the opening.
Rectangular ducts must have a minimum dimension of no less than 3 in (76 mm).
All screens must have mesh ¼" or larger.
Moveable louvers must be locked open or interconnected with the equipment so that they open automatically during
operation.
Keep louvers and grills clean and free of debris or other obstructions.
Check that air source is clean and free of chemicals
Air for combustion and ventilation must be clean and free of corrosive or flammable chemicals. A failure due to corrosive
chemicals in the air is not covered by the warranty. Combustion air must be free of acid-forming chemicals such as sulfur, fluo-
rine, and chlorine. Be sure that air at the vent inlets is free of such chemicals.
Table 1
Minimum Free Area of Permanent Openings for Ventilation and Combustion Air Supply – Air from outdoor or
indoor spaces.
Based on the total BTU/h input rating for all gas burning appliances within a confined space.
Opening Source
Direct to outdoors*
Vertical ducts
Horizontal ducts
Single Opening
Two permanent openings
to another room**
*These openings connect directly with the outdoors through a ventilated attic, a ventilated crawl space, or through
an outside wall.
**For direction on combining spaces in different stories within the structure, refer to the current edition of the Na-
tional Fuel Gas Code ANSI Z223.1/NFPA 54.
See graphics on next page.
(1.42 m
) per 1,000 BTU/h or when getting air from another room.)
3
3
(645 cm
2
Minimum Free Area
in
cm
1
2
(6.5
2
) per 4,000 BTU/hr (see Figure 1, 2)
in
cm
1
2
(6.5
2
) per 4,000 BTU/hr (see Figure 3)
in
cm
1
2
(6.5
2
) per 2,000 BTU/hr (see Figure 4)
in
cm
2
2
) per 3,000 BTU/hr (see Figure 5)
1
(6.5
in
cm
2
(6.5
2
)
1
per 1,000 Btu/hr
Opening: 100 in
(645 cm
2
Minimum dimension of air openings:
no less than 3 in (76 mm)
19
Page
(645 cm
2
2
(645 cm
) of free area would need 134 in
2
2
÷ 0.75 = 134 in
2
).
2
(see Figure 6)
) MIn
2
Installation Manual
Installation
) . Not appropriate for con-
2
).
2

Advertisement

Table of Contents
loading

This manual is also suitable for:

340hx3540hx3

Table of Contents