Input Registers
Table 34: Input Registers.
Register Address
30001
30002
30003
30004
30005
30006~30007
30008
30009
30010
30011
30013
30014
30015~30100
30101, 30102
30103, 30104
30105~30108
30109
30110
30111
30112
30113
30114
30115
30116
30117
30118
30119
30120
30121
30122
30123~30124
30125
30126
30127
30128
MODBUS PROTOCOL REGISTERS
Common Load Water Output Temperature (Average Value of Individual Load Water Outputs)
Common Load Water Input Temperature (Average Value of Individual Load Water Inputs)
Cycle Failure Information (0 : Common System Error, 1~10 : Error of Corresponding Cycle)
Discharge Temperature of Inverter Compressor 1 of Cycle 1
Discharge Temperature of Inverter Compressor 2 of Cycle 1
Intake Temperature of Inverter Compressor 1 of Cycle 1
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Description
Chiller Controller Version
Entire Operation Current
External Air Temperature
Reserve
Information of Refrigerator Failure (1~5)
Failure Code
Start Waiting Time
Product's Accumulated Operation Time Upper Level
Product's Accumulated Operation Time Lower Level
Reserve
Load Water Output Temperature of Cycle 1
Load Water Input Temperature of Cycle 1
Reserve
Condensation Temperature (Left) of Cycle 1
Condensation Temperature (Right) of Cycle 1
Evaporation Temperature (Left) of Cycle 1
Evaporation Temperature (Right) of Cycle 1
Inverter Compressor 1 Frequency of Cycle 1
Inverter Compressor 2 Frequency of Cycle 1
High Pressure (Left) of Cycle 1
High Pressure (Right) of Cycle 1
Low Pressure (Left) of Cycle 1
Low Pressure (Right) of Cycle 1
Operation Current (Left) of Cycle 1
Operation Current (Right) of Cycle 1
Main EEV's Status Value of Cycle 1 (Left)
Main EEV's Status Value of Cycle 1 (Right)
Reserve
Intake Temperature of Inverter Compressor 2 of Cycle 1