Wipe Indication Procedure - Eaton Cutler-Hammer VCP-WR 18 Series Instructions For The Use, Operation And Maintenance

Red line vacuum circuit breaker elements
Hide thumbs Also See for Cutler-Hammer VCP-WR 18 Series:
Table of Contents

Advertisement

I.B. 8295A61H03
Page 40
ORANGE OR BLACK
BLUE OR RED
WHITE CONTACT SPRINGS
CONTACT SPRINGS
CONTACT SPRINGS
Any part of Red or Gray Indicator Visible
Any part of "T" Shape Indicator Visible
Any part of Indicator Visible
— "Wipe" Satisfactory
— "Wipe" Satisfactory
— "Wipe" Satisfactory
Red or Gray Indicator Not Visible
"T" Shape Indicator Not Visible
Indicator Not Visible
— "Wipe" Unsatisfactory
— "Wipe" Unsatisfactory
— "Wipe" Unsatisfactory
Figure 7-5 Wipe Indication Procedure (Performed Only with Breaker Closed)
Effective 7/97