LG LB-H60BESA0 Installation Manual page 17

Ceiling duct-type air conditioner
Table of Contents

Advertisement

REFRIGERANT PIPING
• Use two spanners when connecting the
refrigerant pipe to the unit.
• Make a bend with a radius as large as
possible.
• Perform air purge with R-22 or vacuum
drying.
• When piping work is finished, check all
joints.
Add refrigerant if piping is over 7.5m.
Capacity
60k Btu/h(3ø)
INSTALLATION OF OUT DOOR UNIT
Select the following location
• A place where the air conditioner can get good ventilation.
• A place where it shall not annoy the neighbors.
• A place where the unit shall be leveled and that can support the weight of unit and
withstand its vibrations.
Keep a maintenance space
Perform the work according to the Service Manual or
Installation Guide.
Addition volume
85 g/m
Installation of Indoor, Outdoor Unit
Indoor
Factory charged
Outdoor
Select a location that satisfies the following
conditions. Install the unit firmly in place.
Above 30Cm
Outdoor unit
Above 30Cm
Above 70Cm
Flared connection (Union)
Use a seemliness tube
Flared connection
(Service valve, Ball valve)
Above 50Cm
Face of wall
Installation Manual 17