Ahri Cooling Rating Tables - Bryant PREFERRED 581J Product Data

Preferred series gas heat/electric cooling packaged rooftop 3 to 8.5 nominal tons
Table of Contents

Advertisement

TABLE 2 – AHRI COOLING RATING TABLE 1- - STAGE COOLING
COOLING
UNIT
STAGES
04A
1
05A
1
06A
1
07A
1
TABLE 3 – AHRI COOLING RATING TABLE 2- - STAGE COOLING
COOLING
UNIT
STAGES
08D
2
09D
2
LEGEND
AHRI
--- Air Conditioning, Heating and Refrigeration
Institute Test Standard
ASHRAE --- American Society of Heating, Refrigerating
and Air Conditioning, Inc.
EER
--- Energy Efficiency Ratio
IEER
--- Integrated Energy Efficiency Ratio
SEER
--- Seasonal Energy Efficiency Ratio
Use of the AHRI Certified
TM Mark indicates a
manufacturer's
participation in the
program For verification
of certification for individual
products, go to
www.ahridirectory.org.
NET
NOM.
COOLING
CAPACITY
CAPACITY
(TONS)
(MBH)
3
36.0
4
48.5
5
57.5
6
73.0
NET
NOM.
COOLING
CAPACITY
CAPACITY
(TONS)
(MBH)
7.5
89.0
8.5
97.0
TOTAL
SEER
POWER (kW)
2.9
15.00
3.7
15.60
4.6
15.20
6.0
N/A
TOTAL
SEER
POWER (kW)
7.4
N/A
8.1
N/A
NOTES:
1. Rated in accordance with AHRI Standards 210/240
(04---06 size) and 340/360 (07---09 size).
2. Ratings are based on:
Cooling Standard: 80_F (27_C) db, 67_F (19_C) wb
indoor air temp and 95_F (35_C) db outdoor air temp.
IEER Standard: A measure that expresses cooling
part---load EER efficiency for commercial unitary air ---
conditioning and heat pump equipment on the basis of
weighted operation at various load capacities.
3. All 581J units comply with ASHRAE 90.1 2001, 2004
Energy Standard for minimum SEER and EER
requirements.
4. 581J units comply with US Energy Policy Act (2005).
To evaluate code compliance requirements, refer to
state and local codes or visit the following website:
http://bcap ---energy.org.
8
EER
IEER
12.50
N/A
13.00
N/A
12.45
N/A
12.00
13.00
EER
IEER
12.00
13.00
12.00
13.00

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents