TABLE 7 – MINIMUM - - MAXIMUM AIRFLOW RATINGS - - NATURAL GAS & PROPANE
UNIT
HEAT LEVEL
581J*04
581J*05
581J*06
581J*07
581J*08
581J*09
MINIMUM
LOW
MED
900
HIGH
LOW
MED
1200
HIGH
LOW
MED
1500
HIGH
LOW
MED
1800
HIGH
LOW
MED
2250
HIGH
LOW
MED
2550
HIGH
COOLING
MAXIMUM
1500
2000
2500
3000
3750
4250
11
HEATING
MINIMUM
MAXIMUM
990
2190
1000
1550
---
---
990
2190
1330
2460
1390
2220
990
2730
1330
2880
1390
2780
990
3640
1330
4750
1390
3750
1900
4750
2100
3900
2270
3780
1900
4750
2100
4560
2270
4250