1. Formulas:
Leaving db = entering db —
Leaving wb = wb corresponding to enthalpy of air leaving coil (h
total capacity (Btuh)
h
= h
LWB
EWB
4.5 x CFM
where h
= enthalpy of air entering coil.
EWB
2. Direct interpolation is permissible. Do not extrapolate.
3. Fan motor heat has not been deducted.
4. All data points are based on 10°F superheat leaving coil, and use of thermal expansion valve device.
5. All units have sweat suction tube connection and a liquid tube connection. For 1-1/8-in. system suction tube, 3/4- x 1-1/8-in. suction tube connection adapter
is available as accessory.
6. Check-Flo-Rater pistons (sized for matched cooling-only systems). Refer to outdoor unit installation instructions for pistons required for other systems.
7. The CD5A and CC5A coils can be used in any properly designed system using R-22 or Puron® refrigerant.
8. Before using maximum cfm shown in table, check coil static pressure drop to ensure system blower can provide necessary static pressure needed for coil
and duct systems.
ACCESSORY PART NO.*
KCAKC1212ECC
KCAKC1312ECC
KCAKC1408ECC
KCAKC1508ECC
KCAKC1604ECC
* Individual casings are sold and shipped in multi-packs as indicated in the 8th and 9th digits.
sensible heat cap.
1.09 x CFM
LWB
ENTERING AIR DRY BULB TEMPERATURE (°F)
79
78
81
82
BYPASS
FACTOR
0.10
0.98
1.96
0.20
0.87
1.74
0.30
0.76
1.53
Interpolation is permissible.
Correction Factor = 1.09 x (1 – BF) x (db – 80)
INDOOR COIL PISTONS
UNIT
CD5AXA018
CC5AXA018
CD5AXA024, W024
CC5AXA024, W024
CD5AXA030, W030
CC5AXA030, W030
CD5AXA036, W036
CC5AXA036, W036
CD5AXA042, W042
CC5AXA042, W042
CD5AXA048, C048, W048
CC5AXC048, W048
CD5AXA060
CC5AXA060
CD5AXW060
CC5AXW060
ACCESSORY EMPTY COIL CASING FOR UNCASED A-COIL
NOMINAL CC5A COIL SIZES
W024, W030, A036
W042, W048, A060
)
77
76
75
83
84
84
Correction Factor
2.94
3.92
4.91
2.62
3.49
4.36
shown below
2.29
3.05
3.82
FACTORY-INSTALLED INDOOR PISTON SIZE
DIMENSIONS (In.) W x H x D
A018, A024, A030
W036, A042, C048
W060
—6—
Under 75
Above 85
Use formula
52
59
67
70
78
84
90
90
14-3/16 x 19 x 21
17-1/2 x 20-1/2 x 21
21 x 22 x 21
24-1/2 x 22 x 21
31-1/2 x 22 x 21

Advertisement

loading

This manual is also suitable for:

Cd5a