10. Connect red wire from "COM" on relay assembly to:
(230V-1PH) − "L1"
(230V-3PH) − "L1"
(460V-3PH) − White Wire-Transformer
See Field Installation Diagram on page 9.
11. Connect short orange wire from relay assembly to
indicator light.
12. Connect short black/white wire from relay assembly
to indicator light.
13. Control panel assemblies vary due to available
control options. Find unused space on control
panel and install relay and indicator light
SPACE IS LIMITED IN CONTROL PANELS ON
SOME MODELS. INSTALL RELAY AND INDICATOR
LIGHT WHERE THERE IS SPACE AVAILABLE.
Manual 7960-918
Page
6 of 9
FIGURE 3
Install Relay and Indicator Light Assemblies
assemblies in control panel using self-drilling
screws provided (see Figure 3).
14. Install door panel switch into panel switch bracket
113-908 (see Figure 4). Door panel switch acts as
interlock safety device to disable UV light source
upon removal of blower access panel preventing UV
exposure.
15. Install panel switch assembly on the left side of
blower partition using self -drilling screw as shown
in Figure 4. Some models may have an air deflector
installed on the blower partition; mount switch
assembly next to the blower partition as shown.