User Data - Test Report - ABB TS3 Instruction Manual

Trip unit test set
Table of Contents

Advertisement

5.6.3
- Test Report
User Data
Nr.
Label
1
Heading
2
Test Nr
3
Date
4
Hour
5
Test
6
S/N
7
Name
8
Note
9
I test
10
Phase
11
Test Time
12
Stop by
13
Frequency
Table6. User data Test Report"
Example of test report:
ABB SACE TS3/ABB
Report
Test Nr:
43/99
Date:
09.06.2007
Hour:
15.35.23
#
Test:
PR112/PD
#
S/N:
H6625Q07A
#
Name:
Rossi P.
#
Note:
Version 1.06
I test:
1749A
Phase:
L2
Trip Time:
5217 ms
Stop by:
TC
Freq.
50 Hz
With " # " are indicated the information manually given by the operator/user.
The others are automatically available.
Test report mentions the "User Data" in memory at the moment of the test.
888.902.6111
Description
Default Heading
Test number (automatically proposed by TS3)
Date of the Test
Time of the Test
Information defined by the user (ex. name)
Information defined by the user (ex. Trip unit serial number)
Information defined by the user (ex. Operator name)
Information defined by the user (ex. Particular note, as electrical plant
reference)
Test Current
Name of the tested phase on trip unit (L1, L2, L3 or N)
Test duration
Action that caused the test end (TC, User, timeout, auto-protection, No Load,
various alarms)
Supplied nominal frequency (50 or 60Hz)
TS3
1SDH000670R0002
www.intellirentco.com
|
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
L3852
11/44

Advertisement

Table of Contents
loading

This manual is also suitable for:

L3852

Table of Contents