Hacr Amp Rating; Factory Option Thru-Base Connections - Carrier WeatherMaster 50GC 04-06 Series Installation Instructions Manual

Single package rooftop cooling only/electric heat unit with puron (r-410a) refrigerant
Hide thumbs Also See for WeatherMaster 50GC 04-06 Series:
Table of Contents

Advertisement

4.
Mount the weatherproof cover to the backing plate as shown
in Fig. 26.
5.
Remove two slot fillers in the bottom of the cover to permit
service tool cords to exit the cover.
6.
Check for full closing and latching.
COVER - WHILE-IN-USE
WEATHERPROOF
BASEPLATE FOR
GFCI RECEPTACLE
Fig. 26 — Weatherproof Cover Installation
Non-Powered Convenience Outlet
This type requires the field installation of a general-purpose 125-v
15A circuit powered from a source elsewhere in the building. Ob-
serve national and local codes when selecting wire size, fuse or
breaker requirements, and disconnect switch size and location.
Route 125-v power supply conductors into the bottom of the utili-
ty box containing the duplex receptacle.
Unit-Powered Convenience Outlet
A unit-mounted transformer is factory-installed to step down the
main power supply voltage to the unit to 115-v at the duplex re-
ceptacle. This option also includes a manual switch with fuse, lo-
cated in a utility box and mounted on a bracket behind the conve-
nience outlet; access is through the unit's control box access panel.
See Fig. 23.
The primary leads to the convenience outlet transformer are not
factory-connected. Selection of primary power source is a custom-
er option. If local codes permit, the transformer primary leads can
be connected at the line-side terminals on the unit-mounted non-
fused disconnect or HACR breaker switch; this will provide ser-
vice power to the unit when the unit disconnect switch or HACR
switch is open. Other connection methods will result in the conve-
nience outlet circuit being de-energized when the unit disconnect
or HACR switch is open. See Fig. 27.
Using Unit-Mounted Convenience Outlets
Units with unit-mounted convenience outlet circuits will often re-
quire that two disconnects be opened to de-energize all power to
the unit. Treat all units as electrically energized until the conve-
nience outlet power is also checked and de-energization is con-
firmed. Observe National Electrical Code Article 210, Branch Cir-
cuits, for use of convenience outlets.
Fuse On Power Type
The factory fuse is a Bussman
screw-in (Edison base) type plug fuse.
Test the GFCI receptacle by pressing the TEST button on the face
of the receptacle to trip and open the receptacle. Check for proper
grounding wires and power line phasing if the GFCI receptacle
does not trip as required. Press the RESET button to clear the
tripped condition.
1. Bussman and Fusetron are trademarks of Cooper Technologies
Company.
GFCI RECEPTACLE
NOT INCLUDED
GASKET
1
"Fusetron" T-15, non-renewable
UNIT
CONNECT
VOLTAGE
AS
208, 230
240
460
480
575
600
Fig. 27 — Powered Convenience Outlet Wiring

HACR AMP RATING

The amp rating of the HACR factory-installed option is based on
the size, voltage, indoor motor and other electrical options of the
unit as shipped from the factory. If field-installed accessories are
added or changed in the field (for example, power exhaust,
ERV), the HACR may no longer be of the proper amp rating and
therefore will need to be removed from the unit. See unit name-
plate and label on factory-installed HACR for the amp rating of
the HACR that was shipped with the unit from the factory
(Fig. 28). See unit nameplates for the proper fuse, HACR or
maximum over-current protection device required on the unit
with field installed accessories.
Fig. 28 — HACR Caution Label

FACTORY OPTION THRU-BASE CONNECTIONS

This service connection kit consists of a
connector and a
3
/
-in. electrical bulkhead connector, connected to
4
an "L" bracket covering the embossed (raised) section of the unit
basepan in the condenser section (see Fig. 29 for shipping posi-
tion). The
/
-in. bulkhead connector enables the low-voltage con-
3
4
trol wires to pass through the basepan. The
16
PRIMARY
TRANSFORMER
CONNECTIONS
TERMINALS
L1: RED + YEL
H1 + H3
L2: BLU + GRA
H2 + H4
L1: RED
H1
Splice BLU + YEL
H2 + H3
L2: GRA
H4
L1: RED
H1
L2: GRA
H2
1
/
-in. electrical bulkhead
2
1
/
-in. bulkhead con-
2