TABLE 32 – MICROBOARD DIGITAL INPUTS
*J9-1
30VDC UNREGULATED SUPPLY
J9-2
UNIT ON/OFF SWITCH
J9-3
PWM TEMP RESET
OR LOAD LIMIT STAGE 2 ON 3, 5 & 6 COMP UNITS
J9-4
LOAD LIMIT STAGE 1
J9-5
FLOW SWITCH AND REMOTE START / STOP
J9-6
SPARE
J9-7
SINGLE SYSTEM SELECT
(JUMPER = SINGLE SYS, NO JUMPER=TWO SYS)
J9-8
CR1 (SYS 1 MOTOR PROTECTOR / HIGH
PRESS CUTOUT)
J9-9
CR2 (SYS 2 MOTOR PROTECTOR / HIGH
PRESS CUTOUT)
TABLE 33 – MICROBOARD ANALOG INPUTS
J4-10
SYS 1 SUCTION PRESS TRANSDUCER OR
SYS 1 LOW PRESS SWITCH
J4-11
UNIT TYPE:
CHILLER =
YCUL CONDENSING UNIT =
J4-12
SYS 1 DISCHARGE PRESSURE TRANSDUCER (OPTIONAL)
J5-11
SPARE
J5-12
SYS 1 COOLER INLET REFRIGERANT TEMP SENSOR (R-407C)
J5-13
SYS 2 COOLER INLET REFRIGERANT TEMP. SENSOR (R-407C)
J5-14
SYS 1 SUCTION TEMP SENSOR (EEV OPTION)
J5-15
SYS 2 SUCTION TEMP SENSOR (EEV OPTION)
J6-7
AMBIENT AIR TEMPERATURE SENSOR
J6-8
LEAVING CHILLED LIQUID TEMPERATURE SENSOR
J6-9
RETURN CHILLED LIQUID TEMPERATURE SENSOR
J7-10
SYS 2 SUCTION PRESSURE TRANSDUCER OR
SYS 2 LOW PRESSURE SWITCH
J7-11
SPARE
J7-12
SYS 2 DISCHARGE PRESSURE TRANSDUCER (op tion al)
J8-5
UNIT/SYS 1 VOLTAGE
J8-6
SYS 2 VOLTAGE
*
The 30 dc unregulated supply is not an input. This voltage originates on the microboard and is used to supply the contacts for the digital
inputs.
YORK INTERNATIONAL
TABLE 34 – MICROBOARD DIGITAL OUTPUTS
NO JUMPER J4-6 TO J4-11
JUMPER J4-6 TO J4-11
TB3-2
SYS 1 COMPRESSOR 1
TB3-3
SYS 1 LIQUID LINE SOLENOID VALVE OR EEV
PILOT SOLENOID
TB3-4
SYS 1 COMPRESSOR 2
TB3-5
SYS 1 COMPRESSOR 3
TB3-6
SYS 1 HOT GAS BYPASS VALVE
TB3-8
SYS 2 COMPRESSOR 1
TB3-9
SYS 2 LIQUID LINE SOLENOID VALVE OR EEV
PILOT SOLENOID
TB3-10
SYS 2 COMPRESSOR 2
TB4-1
SYS 2 COMPRESSOR 3
TB4-2
SYS 1 CONDENSER FAN OUTPUT 1
TB4-4
SYS 1 CONDENSER FAN OUTPUT 2
TB4-5
SYS 1 CONDENSER FAN OUTPUT 3
TB4-6
SYS 2 CONDENSER FAN OUTPUT 1
TB4-8
SYS 2 CONDENSER FAN OUTPUT 2
TB4-9
SYS 2 CONDENSER FAN OUTPUT 3
TB4-10
EVAPORATOR HEATER
TB5-1
SYS 1 ALARM
TB5-2
SYS 2 ALARM
TB5-3
EVAPORATOR PUMP STARTER
TABLE 35 – MICROBOARD ANALOG
OUTPUTS
J10-1/J10-2
SYS 1 EEV OUTPUT
J10-3/J10-4
SYS 2 EEV OUTPUT
J10-5/J10-6
SPARE
J10-7/J10-8
SPARE
FORM 150.62-NM7 (103)