Overcharged Refrigerant Systems - Friedrich VRP12K Service And Parts Manual

Hide thumbs Also See for VRP12K:
Table of Contents

Advertisement

R-410A SEALED SYSTEM REPAIR

Overcharged Refrigerant Systems

Compressor amps will be near normal or higher. Noncondensables can also cause these symptoms. To confirm, remove
some of the charge, if conditions improve, system may be overcharged. If conditions don't improve, Noncondensables are
indicated.
Whenever an overcharged system is indicated, always make sure that the problem is not caused by air flow problems.
Improper air flow over the evaporator coil may indicate some of the same symptoms as an over charged system.
An overcharge can cause the compressor to fail, since it would be "slugged" with liquid refrigerant.
The charge for any system is critical. When the compressor is noisy, suspect an overcharge, when you are sure that the
air quantity over the evaporator coil is correct. Icing of the evaporator will not be encountered because the refrigerant
will boil later if at all. Gauges connected to system will usually have higher head pressure (depending upon amount of
over charge). Suction pressure should be slightly higher.
Figure 502(Overcharged System)
107

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vrp12rVrp24kVrp24rVrp36k

Table of Contents