Chapter 2: Site Preparations; Site Selection; Cabinet Placement - Dell Z9432F-ON Setup Manual

Hide thumbs Also See for Z9432F-ON:
Table of Contents

Advertisement

The Z9432F-ON switch is suitable for installation as part of a common bond network (CBN).
You can install the switch in:
● Network telecommunication facilities
● Data centers
● Other locations where the National Electric Code (NEC) applies
For more information about the Z9432F-ON switch specifications, see Specifications.
NOTE:
Install the switch into a rack or cabinet before installing any optional components.
Topics:

Site selection

Cabinet placement

Rack mounting
Switch ground
Fans and airflow
Power
Storing components
Site selection
Install your equipment in restricted access areas. A restricted access area is one where service personnel can only gain access
using a special tool, lock, key, or other means of security. The authority responsible for the location controls access to the
restricted area.
Ensure that the area where you install your switch meets the following safety requirements:
● The switch is near to an adequate power source. Connect the switch to the appropriate branch circuit protection according
to your local electrical codes.
● The environmental—switch location—continuous temperature range is from 0°C to 45°C (32°F to 113°F).
● The operating humidity is from 5 to 90 percent noncondensing, continuous.
● Install in a dry, clean, well-ventilated, and temperature-controlled room, away from heat sources such as hot cooling vents or
direct sunlight.
● Position away from sources of severe electromagnetic noise.
● Position in a rack or cabinet, or on a desktop with adequate space in the front, back, and sides for proper ventilation and
access
● Install the switch in Information Technology Rooms in accordance with Article 645 of the National Electrical Code and NFPA
75.
● Install the switch in an environment that meets all region- or country-specific occupational safety and health requirements.
For more information about switch storage and environmental temperatures, see Specifications.
Cabinet placement
Install the Z9432F-ON switch only in indoor cabinets that are designed for use in a controlled environment.
Do not install the switch in outside cabinets. For cabinet placement requirements, see
The cabinet must meet minimum size requirements. Airflow must be in accordance with the Electronic Industries Alliance (EIA)
standard. Ensure that there is a minimum of 12.7 cm (5 inches) between the intake and exhaust vents and the cabinet wall.
6
Site preparations
Site preparations
Site
selection.
2

Advertisement

Table of Contents
loading

Table of Contents