LED Indications: Special Cases
All LEDs blinking in unison: See Firmware Updates.
3.2.10

Backup Operation

While the Controller is running, if the input voltage to the Energy Pack falls below 20 Vdc,
the Energy Pack will immediately switch to backup power and signal the Controller to
initiate a memory backup.
The Energy Pack supplies power long enough for the Controller to back up memory and then
turns off power to the Controller. When the input voltage to the Energy Pack returns to
normal, the power-up routine begins.
3.2.11

Service and Maintenance

Replacing the Cap Pack Module
The Cap Pack is typically removed and replaced while power is applied to the Energy Pack
(hot swapped.)
WARNING
When replacing the Cap Pack, potentially hazardous energy could be present. Only handle
by the plastic case. Do not allow a short across the printed wiring assembly components or
connectors.