Testing Battery Status

Initiate a battery status test as follows:
On the WZS, push the Test button on the sensor (see
location on
Figure
60). LED5 on the sensor responds by
indicating the level of battery strength, as shown in the
table below.
Table 36. Battery status indicated by LED5 on the wireless zone sensors
User action
LED state
Solid green for 5 seconds
Solid red for 5 seconds
Press Test
button
No light
Blinking red: 1-blink pattern
None
Cycle repeats every 15 minutes.
(a) Blink pattern is On for 1/4 s, Off for 3/4 s, with 2 s Off between repetitions.
Table 37. Battery status shown on the wireless display sensor
Battery test
User action
symbol
Press Test
button

24 V Power Status Indicator

LED5 on the receiver of all models (see
lights and stays constantly On when 24 V power is normal.

Check Signal Strength on a Site

Use the wireless sensor system to check the signal
strength on a site.
1. Power up a receiver with a 24 V transformer (user
supplied).
2. Associate the sensor to a receiver of the same model
intended for the job.
3. Place the receiver at the desired location.
4. Place or hold the sensor at the desired location.
5. Press the Test button (S5) on the sensor and observe
the signal strength as indicated by LED1, LED2, and
LED3 on model WZS (see
display on model WDS (see
For more information on interpreting the LEDs and the
display symbols that indicate signal strength, see
Signal Strength," page
74.

Replacing Sensor Batteries

Sensor battery type, length of life, and installation are
addressed in this section.
UNT-SVX041D-EN
(a)
repeated 5 times.
Battery test
Indicates...
symbol
Full battery
power.
Figure 59 , page
72)
Figure
60), and on the
Figure 61 , page
73).
"Testing
Diagnostics and Troubleshooting
On the WDS, push the Test button on the sensor (see
location on
Figure
symbol appears on the display. The symbol shown
indicates battery life expectancy (see
Indicates...
Battery is adequate for proper operation.
25% battery life left. Batteries should be replaced.
Batteries life expired or not installed properly, or sensor is defective.
Approximately 14 days of operation remain before the battery is too weak
to power the sensor.
Battery test
Indicates...
symbol
50percent battery
life left.
Battery Type
Battery Damage!
Failure to follow instructions below could result in
battery leakage and, in some cases, cause the safety
release vent to open.
Do NOT attempt to recharge the batteries. The batteries
are manufactured in a ready-to-use state and are NOT
designed for recharging.
Sensor Damage!
Do not attempt to hook up the sensor to a power
supply as it could result in sensor damage.
Use two non-rechargeable 1.5 V lithium AA batteries in the
sensor. To maintain UL rating, use only UL-listed lithium
batteries. The sensor ships with Energizer
already installed. Replacement batteries are available at
Trane Service Parts Centers (p/n X13770035010) or other
local suppliers.
Battery Life
Battery life is five years under normal conditions. If the
sensor is not used for an extended period of time, do one
of the following:
Set the sensor address to 000 to place the sensor into
a low-power hibernation mode.
Remove the batteries.
61). In response, a battery test
Table
Indicates...
25 percent battery life left. Replace batteries.
Flashing symbol indicates that approximately
14 days of operation remain before the battery
is too weak to power the sensor.
NOTICE
NOTICE
®
L91 batteries
37).