Table 12B Electrical Specs W60Ac, W72Ac - Bard 11EER WA Series User's Application Manual

Table of Contents

Advertisement

Rated
Model
Volts
& Phase
W60AC-A00, A0Z
A05
A10
230/208-1
A15
A20
W60AC-B00, B0Z
B06
B09
230/208-3
B15
B18
W60AC-C00, C0Z
C09
460-3
C15
W60ACRC00, RC0Z
RC09
460-3
RC15
W72AC-A00, A0Z
A05
A10
230/208-1
A15
A20
W72AC-B00, B0Z
B06
B09
230/208-3
B15
B18
W72AC-C00, C0Z
C09
460-3
C15
W72ACRC00, RC0Z
RC09
460-3
RC15
 These "Minimum Circuit Ampacity" values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest
version), Article 310 for power conductor sizing. CAUTION: When more than one field power circuit is run through one conduit, the
conductors must be derated. Pay special attention to note 8 of Table 310 regarding Ampacity Adjustment Factors when more than
three (3) current carrying conductors are in a raceway.
 Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.
 Based on 75°copper wire. All wiring must conform to the National Electrical Code and all local codes.
NOTE: The Maximum Overcurrent Protection (MOCP) value listed is the maximum value as per UL 1995 calculations for MOCP (branch-
circuit conductor sizes in this chart are based on this MOCP). The actual factory-installed overcurrent protective device (circuit
breaker) in this model may be lower than the maximum UL 1995 allowable MOCP value, but still above the UL 1995 minimum
calculated value or Minimum Circuit Ampacity (MCA) listed.
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor
wires in accordance with the National Electrical Code and all local codes.
Manual 2100-692H
Page
34 of 44
TABLE 12B
Electrical Specifications − W60AC, W72AC Series
Single Circuit
No.
Field
Maximum
Minimum
Power
External
Circuit
Circuits
Fuse or
Ampacity
Ckt. Brkr.
1
38
50
1
38
50
1
59
60
1 or 2
85
90
1 or 2
111
125
1
28
40
1
28
40
1
34
40
1
52
60
2
N/A
N/A
1
14
20
1
18
20
1
26
30
1
16
20
1
20
20
1
29
30
1
56
60
1
56
60
1 or 2
60
70
1 or 2
86
90
1 or 2
112
125
1
38
50
1
38
50
1
38
50
1
54
60
2
N/A
N/A
1
18
25
1
18
25
1
27
30
1
20
25
1
20
25
1
29
30
Minimum
Field
Circuit
Power
Ground
Ampacity
Wire
Wire
Ckt.
Ckt.
Size
A
B
8
10
8
10
6
10
4
8
59
26
2
6
59
52
8
10
8
10
8
10
6
10
N/A
N/A
34
28
12
12
12
12
10
10
12
12
12
12
10
10
6
10
6
10
6
8
56
26
3
8
60
26
2
6
60
52
8
10
8
10
8
10
6
10
N/A
N/A
38
28
10
10
10
10
10
10
10
10
10
10
10
10
Multiple Circuit
Maximum
External Fuse
Field Power
or
Wire Size
Wire Size
Ckt. Breaker
Ckt.
Ckt.
Ckt.
Ckt.
Ckt.
A
B
A
B
60
30
6
10
10
60
60
6
6
10
40
30
8
10
10
60
30
6
10
10
60
30
6
10
10
60
60
6
6
10
40
30
8
10
10
Ground
Ckt.
A
B
10
10
10
10
10
10
10