Fluke i3000s Instruction Sheet

Fluke i3000s Instruction Sheet

Ac current clamp
Hide thumbs Also See for i3000s:

Advertisement

Quick Links

i3000s
AC Current Clamp
Instruction Sheet
Introducing the i3000s
The i3000s is a clamp-on AC Current Clamp for use with
oscilloscopes and multimeters with banana input using the supplied
Dual Banana to BNC Adapter. The clamp is optimized for
measurement on power distribution systems.
Unpacking
The following items should be included in your Current Clamp box:
Current Clamp
Dual Banana to BNC Adapter (model PM9081/001)
Instruction Sheet (this paper)
Check the contents of the shipping box for completeness. If
something in the box has been damaged or missing, contact your
distributor or the nearest FLUKE sales or service office immediately.
Safety Information
Read First: Safety Information.
To ensure safe operation and service of the
current clamp, follow these instructions:
Read the operating instructions before use and follow all
safety instructions.
Use the Current Clamp only as specified in the operating
instructions, otherwise the clamp's safety features may
not protect you.
Adhere to local and national safety codes. Individual
protective equipment must be used to prevent shock and
arc blast injury where hazardous live conductors are
exposed.
Do not hold the Current Clamp anywhere beyond the
tactile barrier, see Figure 8.
Before each use, inspect the Current Clamp. Look for
cracks or missing portions of the clamp housing or output
cable insulation. Also look for loose or weakened
components. Pay particular attention to the insulation
surrounding the jaws.
Check the magnetic mating surfaces of the clamp jaws;
these should be free of dust, dirt, rust and other foreign
matter.
Never use the clamp on a circuit with voltages higher than
600 V CAT III.
CAT III equipment is designed to protect against
transients in equipment in fixed equipment
installations, such as distribution panels, feeders and
short branch circuits, and lighting systems in large
buildings.
October 1997, Rev.3, 08/05
© 1997 -2005 Fluke Corporation.
All rights reserved.
Printed in the Netherlands
All product names are trademarks
of their respective companies.
Use extreme caution when working around bare
conductors or bus bars. Contact with the conductor could
®
result in electric shock.
Use caution when working with voltages above 60 V dc,
30 V ac rms or 42 V ac peak. Such voltages pose a shock
hazard.
Symbols
May be used on HAZARDOUS LIVE conductors.
Product is protected by double insulation.
Risk of Danger. Important information. See
Instruction Sheet.
Risk of Electric Shock.
Conforms to relevant European standards.
Earth ground
Specifications
SAFETY
Input jaws &
Complies with European
Output float voltage
standards EN/IEC 61010-1
2nd Edition & EN/IEC 61010-
02-032 for 600V CAT III,
pollution degree 2.
CE Conformity
EN/IEC 61010-02-032
ELECTRICAL SPECIFICATIONS
All Electrical Specifications are valid at the following reference
conditions:
Ambient temperature
23±3°C (73±3°F)
Relative Humidity
0 to 85%
48 to 65 Hz
Frequency
< 40 A/m
Continuous external field
Load impedance
1 M
// 47 pF
The current may not contain any DC component
No influence from adjacent currents
The conductor must be centered within the jaw aperture
Current Ranges
30A
300A
3000A
Measuring range
1 to 30A ac
1 to 300A ac
1 to 3000 A ac
Crest factor *
up to 3
up to 3
up to 3
Maximum non-
destructive current:
36A
360A
2400A
continuous
2800A
30min.+30min.
stop
5min.+30min.
4000A
stop
Output signal
10 mV/A
1 mV/A
0.1 mV/A
Basic accuracy
2% of reading
2% of reading
2% of reading
+ 0.1A
+ 0.5A
+ 2A
Additional errors:
with
0.02%/°C
0.02%/°C
0.02%/°C
temperature
(-10 to +50°C)
with position of
1% + 0.1A
1% + 0.1A
1% + 0.1A
conductor in
the clamp
window
with adjacent
0.005A/A
0.005A/A
0.005A/A
conductor
See Figure 1
See Figure 2
See Figure 3
with frequency
(10Hz to 100
kHz)
Phase shift
20° @ 2A
3° @ 20A
3° @ 200A
10° @ 8A
1.5° @ 80A
1.5° @ 800A
5° @ 30A
1° @ 300A
1° @ 3000A
See Figure 4
See Figure 5
See Figure 6
*
This is the maximum permissible ratio between the peak value
of a superimposed transient and the ac rms value.
Bandwidth (-3dB)
10 Hz to 100 kHz
(see Figure 7 for derating)
GENERAL
Clamp Dimensions
310 x 120 x 48 mm
(12.2 x 4.7 x 1.9 in)
Weight
1200 g (42.3 oz)
Cable length
2.1 m (82.6 in)
Maximum conductor size
∅ 64 mm (2.5 in)
Maximum Jaw Opening
90 mm (3.5 in)
Temperature
Operating
-10 to +50°C (+14 to +122°F)
Non-operating
-40 to + 85°C (-40 to +185°F)
Relative Humidity
Operating
0 to 85%, up to +35°C (+95°F)
0 to 75%, up to +50°C (+122°F)
Non-operating
0 to 85%, up to -10°C (+14°F)
0 to 75%, up to +85°C (+185°F)
Altitude
Operating
to 2000 m (6500 ft)
Non-operating
to 12000 m (40000 ft)
FREQUENCY RESPONSE
30A Range
Figure 1. Frequency Response @ 10A
300A Range
Figure 2. Frequency Response @ 10A
3000A Range
Figure 3. Frequency Response @ 100A

Advertisement

loading

Summary of Contents for Fluke i3000s

  • Page 1 0.02%/°C 0.02%/°C 0.02%/°C temperature Conforms to relevant European standards. The i3000s is a clamp-on AC Current Clamp for use with (-10 to +50°C) oscilloscopes and multimeters with banana input using the supplied • with position of 1% + 0.1A 1% + 0.1A...
  • Page 2 To use the Current Clamp, follow these instructions: consequence incorrect handling. THIS WARRANTY IS YOUR ONLY REMEDY. NO OTHER Connect the i3000s Current Clamp to the desired input on the WARRANTIES, SUCH AS FITNESS FOR A PARTICULAR measuring instrument. When you are using a multimeter, use Figure 5.