Creepage Distances And Clearances; Insulation Test Voltages, Routine Test, According To En 61131-2; Power Supply Units - ABB Advant AC500 Manual

Table of Contents

Advertisement

Creepage distances and clearances

The creepage distances and clearances meet the overvoltage category II, pollution degree 2.

Insulation test voltages, routine test, according to EN 61131-2

230 V circuits against other circuitry
120 V circuits against other circuitry
120 V to 240 V circuits against other circuitry
24 V circuits (supply, 24 V inputs/outputs), if they are
electrically isolated against other circuitry
COM interfaces, electrically isolated
FBP interface
Ethernet
ARCNET
230 V circuits against other circuitry
120 V circuits against other circuitry
120 V to 240 V circuits against other circuitry
24 V circuits (supply, 24 V inputs/outputs), if they are
electrically isolated against other circuitry
COM interfaces, electrically isolated
FBP interface
Ethernet
ARCNET

Power supply units

For the supply of the modules, power supply units according to PELV specifications must be used.
____________________________________________________________________________________________________________
V2
AC500 Hardware
2500 V
1500 V
2500 V
500 V
500 V
500 V
500 V
500 V
1350 V
820 V
1350 V
350 V
350 V
350 V
350 V
350 V
1-5
System data
surge 1.2/50 µs
surge 1.2/50 µs
surge 1.2/50 µs
surge 1.2/50 µs
surge 1.2/50 µs
surge 1.2/50 µs
surge 1.2/50 µs
surge 1.2/50 µs
AC 2 s
AC 2 s
AC 2 s
AC 2 s
AC 2 s
AC 2 s
AC 2 s
AC 2 s
AC500 / Issued: 05.2007