Lennox 13J76 Installation Instructions Manual

Outdoor air cfm control kit

Advertisement

Quick Links

©2018
INSTALLATION INSTRUCTIONS FOR OUTDOOR AIR CFM CONTROL KIT (13J76; 613720-01)
USED ON LGH/LCH092-360 PACKAGED ROOFTOP UNITS
Shipping and Packing List
Package 1 of 1 contains:
1- Outdoor air CFM flow control (A24) assembly
Bag assembly containing:
2-#10 - 5/8" Sheet metal screws
1-Wire tie
1-Bracket
6-#10 - 5/8" Self drilling screws
1-Template
2-#10 - 1" Sheet metal screws
Application
Units must be equipped with a supply air variable frequency
drive (VFD), an economizer, and an M3 Unit Controller.
When the supply air VFD is operating at lower speeds the
amount of fresh air pulled into the system may not meet
minimum outdoor air requirements. Based on input from
the O.A. control, the Unit Controller modulates outdoor air
dampers to maintain a constant amount of fresh air
regardless of blower speed.
SENSOR
PACKAGED UNITS KITS
AND ACCESSORIES
507473-02
1/2018
Supersedes 3/2017
Install Collar On Sensor
1- Install collar onto sensor at the 10.5 mark. See figure
1. Secure with the screw provided with sensor.
As with any mechanical equipment, contact with
sharp sheet metal edges can result in personal in­
jury. Take care while handling this equipment and
wear gloves and protective clothing.
Improper installation, adjustment, alteration, ser­
vice or maintenance can cause property damage,
personal injury or loss of life. Installation and ser­
vice must be performed by a licensed professional
HVAC installer or equivalent, service agency, or the
gas supplier
Install Sensor
1- Disconnect power to unit and open access panels.
2- Align the template provided in this kit as shown in
figure 2 or 3. Mark and drill holes. Discard the
template.
SECURE COLLAR TO SENSOR -
100501-02
10.5"
10.5"
FIGURE 1
Page 1
OUTDOOR AIR CFM
CONTROL KIT
CAUTION
WARNING
COLLAR

Advertisement

loading

Summary of Contents for Lennox 13J76

  • Page 1 507473-02 1/2018 CONTROL KIT Supersedes 3/2017 INSTALLATION INSTRUCTIONS FOR OUTDOOR AIR CFM CONTROL KIT (13J76; 613720-01) USED ON LGH/LCH092-360 PACKAGED ROOFTOP UNITS Shipping and Packing List Install Collar On Sensor 1- Install collar onto sensor at the 10.5 mark. See figure Package 1 of 1 contains: 1.
  • Page 2 3- Install the sensor. See figure 4 for 092-152 units and parallel with the air stream. figure 5 for 156-360 units. Secure sensor with two 4- Coil excess probe cable and secure to low voltage #10X5/8” sheet metal screws. harness with wire tie. Note - Make sure the air velocity sensor is aligned POSITION TEMPLATE - 092-152 UNITS BRACKET PROVIDED ONLY...
  • Page 3 Install A24 Control LGH/LCH156-360 UNITS Use a field-provided, 22AWG, 3-wire cable to wire the outdoor air control. Cable should be 30” long for 092-152 units and 120” long for 156-360 units. 1- Remove cover connect SEAL field-provided cable as shown in figure 6. 2- 092-240 &...
  • Page 4 WIRE ROUTING - 092-152 UNITS SENSOR M3 UNIT CONTROLLER CABLE BRACKET P298 CONTROL FIGURE 7 Page 4...
  • Page 5 WIRE ROUTING - 156-360 UNITS ROUTE CABLE THROUGH TUBING M3 UNIT CONTROLLER SENSOR BRACKET (156-240 & 300S ONLY) P298 CABLE CONTROL FIGURE 8 Page 5...
  • Page 6 Configuration ID Setting Velocity Sensor Settings The A24 control is factory-set for 0-10m/s. (0-1968ft/min.) 1- Enable the Outdoor Air Control feature and set the velocity sensor range using the M3 Unit Controller Note - The configuration ID velocity range must be set to SETUP >...

This manual is also suitable for:

613720-01