Setting Equipmet
WARNING
Do not install the furnace on its front or its back. Do
not connect the return air ducts to the back of the
furnace. Doing so will adversely affect the operation
of the safety control devices, which could result in
personal injury or death.
The EL280UH(X)E gas furnace can be installed as shipped
in either the upflow position or the horizontal position.
Select a location that allows for the required clearances
that are listed on the unit nameplate. Also consider gas
supply connections, electrical supply, vent connection,
and installation and service clearances [24 inches (610
mm) at unit front]. The unit must be level.
Units with 1/2 and 3/4 hp blower motor are equipped
with three flexible legs and one rigid leg. The rigid leg
is equipped with a shipping bolt and a flat white plastic
washer (rather than the rubber mounting grommet used
with a flexible mounting leg). See figure 6. The bolt and
washer must be removed before the furnace is placed
into operation. After the bolt and washer have been re-
moved, the rigid leg will not touch the blower housing.
Units with 1/2 or 3/4 HP Blower Motor
FIGURE 6
RIGID LEG
remove shipping bolt and washe
Upflow Applications
Allow for clearances to combustible materials as indicated
on the unit nameplate. Minimum clearances for closet or
alcove installations are shown in figure 7.
Upflow Application Installation Clearances
Left Side
Type of Vent
Connector
Top
*Front
Back
Sides
Vent
Floor
*Front clearance in alcove installation must be 24 in. (610 mm).
Maintain a minimum of 24 in. (610 mm) for front service access.
** 3-1/4 in. if single wall vent pipe is used.
‡For installation on a combustible floor, do not install the furnace
directly on carpeting, tile or other combustible materials other
than wood flooring.
†Left side requires 3 inches if a single wall vent is used on 14-1/2
inch
nets.
Page 8
Top
Right Side
AIR FLOW
Bottom
Type C
Type B1
1 in. (25 mm)
1 in. (25 mm)
2-1/4 in. (57 mm)**
2-1/4 in. (57 mm)
0
0†
6 in. (152 mm)
1 in. (25 mm)
0‡
FIGURE 7
0
0
0‡