16 - Vent connectors serving Category I appliances shall
not be connected to any portion of mechanical draft
systems operating under positive pressure such as
Category III or IV venting systems.
17 - If vent connectors are combined prior to entering
the common vent, the maximum common vent
capacity listed in the common venting tables must
be reduced by 10%, the equivalent of one 90° elbow
(0.90 x maximum common vent capacity).
18 - The common vent diameter must always be at least
as large as the largest vent connector diameter.
19 - In no case, shall the vent connector be sized more
than two consecutive table size diameters over the
size of the draft hood outlet or flue collar outlet.
Lateral
Height
H
L
(feet)
(feet)
0
2
6
4
6
0
2
8
5
8
0
2
10
5
10
0
2
15
5
10
15
0
2
5
20
10
15
20
0
2
5
30
10
15
20
30
NOTE - Single appliance venting configurations with zero lateral lengths are assumed to have no elbows in the vent system. For
all other vent configurations, the vent system is assumed to have two 90° elbows. For each additional 90° elbow or equivalent (for
example two 45° elbows equal one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by
10 percent (0.90 x maximum listed capacity).
Capacity of Type B Double-Wall Vents with Type B Double-Wall Connectors
Serving a Single Category I Appliance
3 inch
Appliance Input Rating in Thousands of Btu Per Hour
Min
Max
0
78
13
51
21
49
25
46
0
84
12
57
23
53
28
49
0
88
12
61
23
57
30
51
0
94
11
69
22
65
29
59
35
53
0
97
10
75
21
71
28
64
34
58
48
52
0
100
9
81
21
77
27
70
33
64
56
58
NA
NA
20 - Do not install a manual damper, barometric draft
regulator or flue restrictor between the furnace and
the chimney.
21 - When connecting this appliance to an existing
dedicated or common venting system, you must
inspect the venting system's general condition
and look for signs of corrosion. The existing vent
pipe size must conform to these instructions and
the provided venting tables. If the existing venting
system does not meet these requirements, it must
be resized.
TABLE 3
Vent and Connector Diameter - D (inches)
4 inch
Min
Max
0
152
18
97
30
94
36
91
0
165
16
109
32
103
39
98
0
175
17
118
32
113
41
104
0
191
15
136
30
130
40
121
48
112
0
202
14
149
29
143
38
133
46
124
55
116
0
213
13
166
28
160
37
150
44
141
53
132
73
113
Page 18
5 inch
Min
Max
Min
0
251
27
157
39
153
47
149
0
276
25
178
42
171
51
164
0
295
23
194
41
187
54
176
0
327
20
226
39
219
51
206
61
195
0
349
18
250
38
242
50
229
59
217
69
206
0
374
14
283
36
275
48
262
57
249
66
237
88
214
104
6 inch
Max
0
375
32
232
50
227
59
223
0
415
28
263
53
255
64
247
0
447
26
289
52
280
67
267
0
502
22
339
49
330
64
315
76
301
0
540
20
377
47
367
62
351
73
337
84
322
0
587
18
432
45
421
59
405
70
389
80
374
346

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

El280uheEl280uhxe

Table of Contents