Clearances
Refer to Figure 1 for minimum clearance requirements.
Wall
Flow
Wall
NOTE - No part of the suspended ceiling, or other supports not directly associated with the indoor unit installation,
can be fixed to, or touch the indoor unit, in any form. Minimum clearances must be observed at all times.
NOTE - Horizontal installation only.
20" (508 mm) Minimum Service Clearance
Air
DUCTED
UNIT
24" (610 mm)
Minimum
Service
Clearance

TOP VIEW

Ceiling
24" (610 mm) Minimum Clearance
1" (25 mm) Minimum Clearance
Suspended
Ceiling

FRONT VIEW

Figure 1. Minimum Installation Clearances
Minimum
Service
24" (610 mm)
Clearance
To ensure full fan deck removal a minimum
distance of 24" (610 mm) should be
between the unit and ceiling or closest
obstruction.