Control Wiring - Cooper Lighting LRM347 Technical Data Manual

Lighting relay module
Table of Contents

Advertisement

Available languages

Available languages

vii. You can alter output levels collectively or
individually, as required:
Collectively - Highlight the "All Outputs"
option and either type the required dimming
level using the keypad or use the
buttons to adjust the current value for all
outputs and press the
Individually - Highlight the required output and
either type the required dimming level using
the keypad or use the
adjust current value and press the
to set the output value.
viii. To exit, press the
and return to the previous screen.

Control Wiring

For Emergency Panel configurations, ensure the iLumin SC
panel is fed from an emergency power source.
The LRM provides a dry contact maintained closure to the
switch input 1 or switch input 2 terminal on the iLumin SC
panel input card.
Emergency actions can be programmed from the iLumin SC
panel on board user interface.
or
button.
ENT
or
buttons to
ENT
button to save all changes
ESC
button
Ilumin Contact Inputs
Yellow (18AWG)
SPDT
Relay
Switch
Switch
Input 1
Input 2
To override ON:
Connect Dry Contact From LRM to
Switch Input 1 or Switch Input 2.
When contact Closes, All Relays/
Dimmers are Forced On Full.
Contacts of the LRM will Close
When normal Power is Lost.
Violet
NC
C
(18AWG)
NO
To Normal Power Circuit
347VAC = Brown
(16AWG)
Neutral = White
(16AWG)
Wiring Diagram
www.cooperlighting.com
Control Wiring
Switch
Switch
Input 1
Input 2
Contact Closure
3

Advertisement

Table of Contents