Application Guidelines Scroll compression principle Scroll compressor The motor stator is rigidly attached to the shell. shaft is supported by two bearings, one in the components The rotor is shrink-fit onto the eccentric shaft. The crankcase and the second below the motor. FRCC.PC.017.A2.02...
SUCTION COMPRESSION DISCHARGE Danfoss Heat Pump scroll compressors are and the factory, very high standards of reliability manufactured using most advanced and process control were first priority.
Application Guidelines Compressor model designation Nomenclature Type Size Motor Features Application: Other features H: high temperature Gas equali- Oil sight Oil equali- LP gauge sation port glass drain sation port None None None None None Family: HP: heat pump R407C PVE Tubing and electrical connections P: brazed connections, spade terminals C: brazed connections, screw terminals...
Superheat: 10 K Subcooling: 5 K Subject to modification without prior notification Conditions: 400V/3ph/50Hz (motor T4), 230V/1ph/50 Hz (motor T5) For full data details and capacity tables refer to Online Datasheet Generator : www.danfoss.com/odsg Performance table Model 2 550 3 070...
Application Guidelines Electrical data, connections and wiring Motor voltage Danfoss Heat Pump scroll compressors are available in 2 different motor voltages. Motor voltage code 4 Motor voltage code 5 Nominal voltage 50 Hz 380-400V-3-50 Hz 220-240V-1-50 Hz Voltage range 50 Hz...
25°C, the measured resistance must be corrected with following formula: Electrical connections The Danfoss Heat Pump scroll compressors are running within the defined nominal voltage. PSC designed to operate without any assistance if wiring is sufficient (see below).
HHP026T5LP6 HHP030T5LC6 HHP038T5LC6 Internal motor protection The Danfoss Heat Pump scroll compressors are If the internal overload protector trips out, it must equipped with an internal line break protector cool down to about 60°C to reset. Depending on mounted on the motor windings. The protector...
Application Guidelines Approvals and certifications Approvals and certificates The Danfoss Heat Pump scroll compressors Certificates are listed on the product datasheets: comply with the following approvals and http://www.danfoss.com/odsg certificates. CE 0062 or CE 0038 All models (European Directive) All models...
The PVE lubricant is compatible with R22 which makes the Danfoss Heat Pump scroll compressors a very versatile multi- refrigerant solution. Motor supply The Danfoss Heat Pump scroll compressors can...
DGT compressor! protection is required (n°1) and where it is not (n°2). A DGT accessory is available from Danfoss: refer to section "Spare parts and accessories". FRCC.PC.017.A2.02...
(loss of charge safety switch) setting is also listed in the table above. On/off cycling (cycle rate Danfoss recommends a restart delay timer to limit cooling after start-up along with proper oil return. limit) compressor cycling. The timer prevents reverse...
Application Guidelines System design recommendations General Successful application of scroll compressors is for the system, it will operate beyond the limits dependent on careful selection of the compressor given in this manual. Poor performance, reduced for the application. If the compressor is not correct reliability, or both may result.
Application Guidelines System design recommendations Refrigerant charge limit Danfoss Heat Pump scroll compressors can Use the tables below to quickly evaluate the tolerate liquid refrigerant up to a certain extend required compressor protection in relation without major problems. However, excessive with the system charge and the application.
Page 21
Application Guidelines System design recommendations Heat pumps NON- NON- INDOOR COIL BLEED BLEED Expansion device NON- OUTDOOR COIL BLEED BLEED Expansion device <3.6 kg SYSTEM CHARGE >3.6 kg <5.4 kg >5.4 kg TEST REQUIRED ACCEPTABLE SUMP SUPERHEAT TEMPERATURE ACCUMULATOR REQUIRED INDOOR COIL BLEED BLEED...
6K to 17K above saturated suction section "System design recommendations". Loss of charge protection Danfoss Heat Pump scroll compressors do not • A discharge line thermostat set no higher than include a thermal valve protection; therefore, 140°C is recommended. The thermostat must...
Because of the Danfoss’s unique design of a full- also do not generate the penetrating power of suction gas & oil cooled motor, compressor body lower-frequency sound.
Application Guidelines Installation Each Danfoss Heat Pump scroll compressor is shipped with printed Instructions for installation. System cleanliness The refrigerant compression system, regardless System contamination is one of main factors of the type of compressor used, will only provide affecting equipment reliability and compressor high efficiency and good reliability, along with a service life.
The compressor should not be exposed to the open air for extended The PVE oil used in Danfoss Heat Pump scroll periods. compressors is highly hygroscopic and will •...
Remove and replace the liquid line filter burnout drier and the liquid line and suction line drier and install a Danfoss type DAS burnout drier filter driers. of appropriate capacity. FRCC.PC.017.A2.02...
Compressors are packed individually in a cardboard box. They can be ordered in any quantity. Minimum ordering quantity = 1. As far as possible, Danfoss will ship the boxes on full pallets of 6 compressors according below table. • Each box also contains following accessories: •...
Page 33
Compresseurs scroll Danfoss pour la réfrigération Efficacité et fiabilité élevées, même à de basses températures Plus frais que jamais ! Les séries MLZ et LLZ pour la réfrigération moyennes et basses températures, sont efficient par design. Répondez aux normes agro-alimentaires les plus strictes et réduisez les coûts de fonctionnement.
Page 34
Compresseurs scroll de Danfoss destinés aux applications de réfrigération Les séries MLZ et LLZ ont été spécialement conçues pour les applications de réfrigération moyennes et basses températures. Elles conviennent à un large éventail de conditions de fonctionnement dans divers systèmes de refroidissement.
Page 35
Avec injection de vapeur avec l’injection de vapeur Température d’évaporation(°F) à de basses températures Danfoss vous propose, en option, le kit économiseur pour améliorer l’efficacité du compresseur et sa puissance à l’aide RGT : 20 °C / 68 °F de l’injection de vapeur.
Page 36
R134A MLZ – applications moyennes températures 50Hz PUISSANCE FRIGORIFIQUE EN W / TEMPÉRATURE DE CONDENSATION 40 °C EN12900 Puissance Puissance Puissance frigorifique absorbée sonore Modèle -15 °C -10 °C -5 °C 0 °C 5 °C 10 °C 15 °C en W en kW dB(A) MLZ015 1 650 2 100 2 640 3 280...
Page 37
R404A MLZ – applications moyennes températures 50 Hz PUISSANCE FRIGORIFIQUE EN W / TEMPÉRATURE DE CONDENSATION 40 °C EN12900 Puissance Puissance Puissance frigorifique absorbée sonore Modèle -25 °C -20 °C -15 °C -10 °C -5 °C 0 °C 5 °C 10 °C en W en kW dB(A) MLZ015 1 660 2 180 2 770 3 450...
Page 38
Danfoss n’assume aucune responsabilité quant aux erreurs qui se seraient glissées dans les catalogues, brochures ou autres documentations écrites. Dans un souci constant d’amélioration, Danfoss se réserve le droit d’apporter sans préavis toutes modi cations à ses produits, y compris ceux se trouvant déjà en commande, sous réserve, toutefois, que ces modi cations n’a ectent pas les caractéristiques déjà...
Page 39
Guide de sélection et d’application RECIPROCATING COMPRESSORS MT/MTZ 50 Hz R407C R134a R404A / R507 1 CYLINDRE 2 CYLINDRES 4 CYLINDRES 8 CYLINDRES Refrigeration and Demandez-nous Air Conditioning toujours plus...
Danfoss Maneurop Compresseurs à Pistons Les compresseurs hermétiques à pistons Danfoss Maneurop sont spécialement conçus pour pouvoir être utilisés dans une vaste plage de conditions de fonctionnement. Toutes les pièces sont réalisées avec une grande précision et une qualité supérieure pour garantir une durée de vie maximale.
Plages d’application Plage d’application pour les compresseurs MT au S.H. = 11.1 K S.H. = 30 K Température d'évaporation (°C) Plage d’application pour les compresseurs MTZ au R407C S.H. = 11.1 K S.H. = 30 K au point de rosée Température d'évaporation (°C) Plage d’application pour les compresseurs MTZ au...
Page 47
Selon les recommandations fluide frigorigène est généralement Glissement de température : de l’Asercom, Danfoss Maneurop décrit comme presque azéotrope. Durant les phases d’évaporation utilise les températures de rosée Le R404A est classé dans cette et de condensation, à...
Tables de performances Modèles P.F. P.A. P.F. P.A. P.F. P.A. P.F. P.A. P.F. P.A. P.F. P.A. P.F. P.A. P.F. P.A. P.F. P.A. 0.59 1 240 0.69 1 740 0.79 2 360 0.88 3 120 0.95 4 040 1.00 5 140 1.04 6 430 1.04...
Page 49
Tables de performances Modèles P.F. P.A. P.F. P.A. P.F. P.A. P.F. P.A. P.F. P.A. P.F. P.A. P.F. P.A. P.F. P.A. P.F. P.A. 4 850 2.64 6 670 2.99 8 820 3.35 11 340 3.69 14 260 4.01 17 610 4.30 21 430 4.56 25 750...
Tables de performances R134a Modèles P.F. P.A. P.F. P.A. P.F. P.A. P.F. P.A. P.F. P.A. P.F. P.A. P.F. P.A. P.F. P.A. 0.60 1 290 0.67 1 790 0.73 2 380 0.78 3 070 0.82 3 880 0.84 4 820 0.84 5 890 0.83 0.62...
Page 53
Tables de performances R134a Modèles P.F. P.A. P.F. P.A. P.F. P.A. P.F. P.A. P.F. P.A. P.F. P.A. P.F. P.A. P.F. P.A. 5 700 3.16 7 880 3.52 10 560 3.85 13 790 4.14 17 650 4.36 22 210 4.50 27 520 4.55 33 670 4.49...
Tables de performances R404A / R507 Modèles P.F. P.A. P.F. P.A. P.F. P.A. P.F. P.A. P.F. P.A. P.F. P.A. P.F. P.A. P.F. P.A. P.F. P.A. 0.67 1 210 0.78 1 640 0.87 2 170 0.95 2 830 1.02 3 640 1.07 4 590 1.09...
Page 55
Tables de performances R404A / R507 Modèles P.F. P.A. P.F. P.A. P.F. P.A. P.F. P.A. P.F. P.A. P.F. P.A. P.F. P.A. P.F. P.A. P.F. P.A. 5 660 3.88 7 590 4.44 10 020 4.97 13 050 5.45 16 730 5.85 21 150 6.16 26 380...
Dimensions 1 CYLINDRE Boîte à bornes Voyant d'huile (modèle VE uniquement) Connecteurs (plats) 1/4” AMP-AWE Borne de terre M4-12 Opercule Ø 21 mm 55˚ Ø 21 mm Indice de protection : IP 55 (avec presse étoupe) Ø 225 Modèle avec code moteur 3,4 et 6 forme enveloppe supérieure arrondie...
Dimensions 2 CYLINDRES Boîte à bornes Trou de fixation pour la résistance de carter PTC Connecteurs (plats) 1/4” AMP-AWE Borne de terre M4-12 Opercule Ø 21 mm 37˚ Ø 21 mm Indice de protection : IP 55 (avec presse étoupe) Boîte à...
Dimensions 4 CYLINDRES Trou de fixation Boîte à bornes pour la résistance Voyant d'huile de carter PTC (modèle VE uniquement) 10-32 UNF x 9,5 Borne de terre M4-12 Opercule Ø 29 mm Ø 29 mm Indice de protection : IP 54 (avec presse étoupe) Boîte à...
Dimensions 8 CYLINDRES Égalisation d'huile Boîte à bornes 10-32 UNF x 9,5 Ø 29 mm Borne de terre M6 Opercule Ø 29 mm Opercule Ø 21 mm Indice de protection : IP 55 (avec presse étoupe) Prise de pression BP(schrader) Ø...
Caractéristiques électriques et schémas de câblage SCHÉMAS DE CÂBLAGE CONSEILLÉS 230 V Monophasé Câblage PSC avec Ω “trickle circuit” 220 k - 1 W µ Thermostat C : Commun / S : Phase de démarrage (auxiliaire) / R : Phase principale (marche) A &...
50% par rapport à la durée de vie de ces pièces pour les compresseurs triphasés. valeur nominale Pour ces réglementations, Danfoss • peuvent être utilisés sur les installations Note importante : le nombre de Maneurop offre des kits de démarrage existantes utilisant les compresseurs démarrage doit être limité...
Informations générales et normes MARQUES DE CONFORMITÉ NORMES VERBAND UNDERWRITERS EUROPEAN FRANÇAISES DEUTSCHER LABORATORIES INC. DIRECTIVE ELEKTROTECHNIKER La plupart des compresseurs Maneurop ® MT / MTZ répondent aux normes internationales de sécurité et sont approuvés par les organismes ci-dessus. Tous les modèles MT & MTZ sont marqués CE. Se référer au bulletin technique TI2-011 pour une liste détaillée. INDICE D’ÉVOLUTION TECHNIQUE EX: MT125 HU 4 D VE MT 18...
Divers INDICE DE PROTECTION IP Les indices de protection IP des boîtiers de raccordement électrique sont indiqués sur les plans des compresseurs (voir pages correspondantes). Lettre de désignation Les informations ci-contre indiquent les différentes combinaisons possibles Premier chiffre suivant la norme CEI 529. Degré...
Note : la charge initiale 160P doit-être à base de R22 remplacée par de l’huile 160ABM. Hydrocarbones Danfoss Maneurop n’autorise pas l’utilisation des hydrocarbones dans ses compresseurs Selon le protocole de Montréal Aussi, les performances et autres avec ces fluides frigorigènes et peuvent les fluides frigorigènes CFC tels que...
Page 67
Les hydrocarbones tels que propanes, cas l’utilisation de ces fluides même avec une charge réduite en isobutanes, … etc sont très inflammables. frigorigènes hydrocarbones avec les fluide frigorigène. Danfoss Maneurop n’autorise en aucun compresseurs Maneurop MT ou MTZ Catalogue 50 Hz RECIPROCATING COMPRESSORS...
être calculé pour fonctionne (vitesse 8 à 12 m/s). rotolock, qui peuvent être fournies garantir une vitesse minimale des gaz comme accessoire par Danfoss de 4 m/s. La section équivalente des tubes Maneurop, sont définies au diamètre Dans les parties verticales, la vitesse montants doit être calculée pour une...
Recommandations système Tuyauteries de refoulement où la longueur des tuyauteries excède voyant liquide, etc..., doivent toujours Lorsque le condenseur est implanté 20 m, ayant plusieurs pièges à huile où être sélectionnés en fonction du fluide au-dessus du compresseur, un piège bien possédant un séparateur d’huile, frigorigène utilisé.
Recommandations système PLAGE DE TENSION ET CYCLAGE MOTEUR Plage de tension d’utilisation décrites dans ce tableau. génèrent des surintensité dans une Les limites d’application en plage de La différence de tension maximale ou plusieurs des phases moteur tension sont spécifiées dans le tableau entre phases pour le moteur triphasé...
Page 71
Recommandations système Retour du fluide frigorigène au Les conséquences négatives de ce type d’importants retours liquide, des coups compresseur de fonctionnement sont : de liquide pourront se produire En régime de fonctionnement normal • dilution permanente de l’huile et stabilisé, le fluide frigorigène quitte •...
Page 72
Recommandations système Résistance de carter d’huile à 10 K au-dessus de la tempé- à distance, groupe de condensation et Une résistance de carter protège le rature de gaz saturé dans l’enveloppe installations “split-system”. compresseur contre les migrations de du compresseur pendant les périodes Tous les compresseurs 8 cylindres sont fluide frigorigène pendant les périodes d’arrêt.
Un soin particulier doit être pris pour tions fixes en A/C ou réfrigération. vibratoires. éviter de réaliser une tuyauterie ayant Danfoss Maneurop ne garantit pas ces Le compresseur ne doit jamais être une fréquence de résonance proche mêmes compresseurs en application assemblé...
Installation et maintenance PROPRETE DU CIRCUIT La qualité mise en œuvre lors du • Humidité et air. mettre en place une vanne schrader, montage d’une installation contribue très Utiliser uniquement du tube cuivre de par exemple), les limailles et copeaux largement à...
Installation et maintenance Lorsque des vannes rotolock sont Schrader prévues sur le compresseur elles doivent être fermées immédiatement après montage, afin d’isoler le compresseur de l’ambiance d’une part ou du circuit non encore déshydraté d’autre part. Note : dans le cas d’un montage en centrale, par exemple, en atelier et non pas sur le site définitif, un tirage au vide poussé...
Installation et maintenance un niveau de vide de 500 microns s’accroît rapidement, le système d’humidité dans l’installation peut (0.67 mbar). n’est pas étanche. atteindre 100 ppm. Une pompe à vide appropriée Procéder de nouveau à une opération En fonctionnement, l’utilisation d’un à...
Page 77
Installation et maintenance faible que possible car elle s’avère être correct, il est impératif - la présence de gaz incondensables augmente les performances de de vérifier l’isolation de la ligne - une surchauffe excessive compresseur et aussi sa durée de vie. d’aspiration entre l’évaporateur et le - une charge de réfrigérant trop A noter, cependant, que des valeurs...
Page 78
Tous les efforts ont été faits pour publier les performances et descriptions les plus précises possibles. Cependant, du fait de l’amélioration et l’évolution constante de nos produits, ces informations sont susceptibles d’être modifiées sans avis préalable. Maneurop ® est une marque de Danfoss.
Page 81
Application Guidelines Content Features ............ 4 System design recommendations ..34 General ..................34 Scroll compression principle ....5 Essential piping design considerations .....34 The scroll compression process........5 Refrigerant charge limit ..........35 Off-cycle migration ............35 Compressor model designation ..... 6 Liquid flood back ...............37 Nomenclature ...............6 Specific application recommendations 38 Label ..................6...
Page 82
Features With its unique scroll design and manufacturing are engineered for refrigeration, and offer process flexibility, the new Danfoss MLZ/ cooling capacity from 3.4 to 21 kW (2 to 10 HP) MLM refrigeration compressor offers a highly at common voltages and frequencies as well...
SUCTION COMPRESSION DISCHARGE Danfoss scroll compressors are manufactured standards of reliability and process control using the most advanced machining, assembly, were first priority. The result is a highly efficient and process control techniques. In design of...
Application Guidelines Compressor model designation Nomenclature Type Size Motor Features M LZ T 4 L Application Other features M: medium temperature refrigeration Oil equali- LP gauge Oil sight Gas equalisa- sation drain port glass tion port Threaded None Schrader None None Family, Refrigerant &...
37300 11.30 Legend: To: Evaporating temperature in °C Qo: Cooling capacity in W RGT= 20°C Tc: Condensing temperature in °C Pe: Power input in kW Subooling= 0K Capacity data at other conditions are available in the datasheets at: www.danfoss.com/odsg FRCC.PC.015.A8.02...
Legend: To: Evaporating temperature in °C Qo: Cooling capacity in W RGT = 20°C Tc: Condensing temperature in °C Pe: Power input in kW Subcooling =0 K Capacity data at other conditions are available in the datasheets at: www.danfoss.com/odsg FRCC.PC.015.A8.02...
Legend: To: Evaporating temperature in °C Qo: Cooling capacity in W RGT = 20°C Tc: Condensing temperature in °C Pe: Power input in kW Subcooling =0 K Capacity data at other conditions are available in the datasheets at: www.danfoss.com/odsg FRCC.PC.015.A8.02...
Qo: Cooling capacity in W RGT = 20°C Tc: Condensing temperature in °C Pe: Power input in kW Subcooling =0 K Capacity data at other conditions are available in the datasheets at: www.danfoss.com/odsg Only motor code4.code5 of MLZ are qualified with R407A FRCC.PC.015.A8.02...
Qo: Cooling capacity in W RGT = 20°C Tc: Condensing temperature in °C Pe: Power input in kW Subcooling =0 K Capacity data at other conditions are available in the datasheets at: www.danfoss.com/odsg Only motor code4.code5 of MLZ are qualified with R407F FRCC.PC.015.A8.02...
Application Guidelines Dimensions Oil sight glass MLZ / MLM scroll compressors come equipped with a threaded oil sight glass with 1"1/8 - 18 UNEF connection. It can be used for a visual Oil sight glass check of the oil amount and condition or it may Schrader valve be replaced by an accessory oil management and cap...
Application Guidelines Electrical data, connections and wiring Motor voltage MLZ/MLM scroll compressors are available in 6 different motor voltages. Motor voltage Motor voltage Motor voltage Motor voltage Motor voltage Motor voltage code 1 code 2 code 4 code 5 code 7 code 9 200-220 V - 3 ph 380-415 V - 3 ph...
Application Guidelines Electrical data, connections and wiring LRA (Locked Rotor Amp) LRA is the higher average current as measured The LRA value can be used as a rough estimation on a mechanically blocked compressor tested for the starting current. However in most cases, under nominal voltage.
Application Guidelines Electrical data, connections and wiring remains at high temperature and thus at high internal protector to open and would cause even resistance as long as power is connected to the further delay until the overload is reset. compressor. When the compressor is switched off, the PTC cools down to its initial low resistance The following PTC types are recommended for and becomes available to support the next...
Application Guidelines Electrical data, connections and wiring Three phase CONTROL CIRCUIT Suggested wiring diagram with "one shot" pump down cycle and safety lock-out relay 180 s Control device ..........TH Optional short cycle timer (3 min) ..180 s Control relay ............ KA Liquid Line Solenoid valve ......LLSV Compressor contactor ........
All MLZ models (European Directive) Models with motor code 1, 5 except when using (Underwriters Laboratories) PTCSCR system Other approvals / certificates Contact Danfoss Conformity to directives Pressure equipment directive 2014/68/EU Low voltage directive 2014/35/EU Machinery directive 2006/42/EC Products MLZ / MLM 015 to 076...
Application Guidelines Operating conditions • Refrigerant and lubricants The scroll compressor application range is • Motor supply influenced by several parameters which need to • Compressor ambient temperature be monitored for a safe and reliable operation. • Application envelope (evaporating These parameters and the main recommendations for good practice and safety temperature, condensing temperature, return...
Page 105
According to and rise in the evaporator. Therefore when EN12900 recommendations, Danfoss Commercial speaking about evaporating and condensing Compressors use dew point temperatures for temperatures, it is important to indicate whether selection tables and application envelopes etc.
Application Guidelines Operating conditions Motor supply MLZ / MLM scroll compressors can be operated ranges. In case of risk of under-voltage operation, at nominal voltages as indicated in table section special attention must be paid to current draw “Motor voltage”. Under-voltage and over-voltage and start assist for single-phase compressors may operation is allowed within the indicated voltage be required.
Page 107
Application Guidelines Operating conditions MLZ - R134a SH 11K Evaporating temperature (°C) MLZ / MLM - R22 SH: 11K RGT: 25°C Evaporating temperature (°C) FRCC.PC.015.A8.02...
DGT compressor! protection is required (n°1) and where it is not (n°2). A DGT accessory is available from Danfoss: refer to section “Spare parts & accessories”. MLZ / MLM R22 - SH 11K Example 1 ...
12 starts per hour can reduce the service life depends upon system design. of the motor-compressor unit. A one-minute time out is recommended. Danfoss recommends a restart delay timer to limit compressor cycling. The system must be designed in a way that provides a minimum compressor running time...
Application Guidelines System design recommendations General Successful application of scroll compressors beyond the limits given in this manual. Poor is dependent on careful selection of the performance, reduced reliability, or both may compressor for the application. If the compressor result. is not correct for the system, it will operate Essential piping design Proper piping practices should be employed to...
More detailed information can be found in the place in the compressor and/or the suction line instead of the evaporator. System design must be paragraphs hereafter. Please contact Danfoss for such that the amount of liquid refrigerant in the any deviation from these guidelines.
Page 114
Belt-type crankcase heater accessories are Optimum location area available from Danfoss (see section “Spare parts & Accessories”). The heater must be energized whenever the compressor is off. Provide separate electrical supply for the heaters so that they remain energized even when the machine is out of service (eg.
Application Guidelines System design recommendations • While the thermostat is off, the number of Other application needs a liquid receiver to store pressure switch resets should be limited to the refrigerant. avoid short cycling of the compressor. Use dedicated wiring and an additional relay which Receiver dimensioning requires special attention.
Several possible solutions are discharge line. available to prevent the risk of compressor to For further information, please contact Danfoss. vacuum and low pressure differential between the suction and discharge pressures. Scroll and reciprocating...
Application Guidelines Specific application recommendations Low load operations The compressor should be run for a minimum that the motor receives enough cooling under period to ensure that the oil has sufficient time conditions of lowest refrigerant mass flow. to properly return to the compressor sump and Brazed plate A brazed plate heat exchanger needs very Due to the small volume of the brazed plate heat...
Application Guidelines Sound and vibration management Starting sound level During start-up transients it is natural for the compressor rotation is characterized by an compressor sound level to be slightly higher objectionable sound. To correct reverse rotation, than during normal running. MLZ/MLM scroll disconnect power and switch any two of the compressors exhibit very little increased start-up three power leads at the unit contactor.
Application Guidelines Sound and vibration management Mechanical vibrations Vibration isolation constitutes the primary In addition, it is extremely important that the method for controlling structural vibration. frame supporting the mounted compressor be MLZ/MLM scroll compressors are designed to of sufficient mass and stiffness to help dampen produce minimal vibration during operations.
Application Guidelines Installation Each MLZ/MLM compressor is shipped with www.danfoss.com or directly from: printed Instructions for installation. These http://instructions.cc.danfoss.com Instructions can also be downloaded from our web site System cleanliness The refrigeration system, regardless of the type mesh screen and can cause considerable damage of compressor used, will only provide high within a bearing assembly.
Page 121
Remaining flux would cause corrosion of the contact the product manufacturer or distributor. tubing. For specific applications not covered herein, please contact Danfoss for further information. Ensure that no flux is allowed to enter into the tubing or compressor. Flux is acidic and can cause Brazed...
50 ppm end point dryness After burn out, remove & replace the liquid (EPD). Danfoss recommends DCL (solid core) line filter drier and install a Danfoss type DAS burnout drier of the appropriate capacity. Refer driers for the MLM compressor (R22 with...
Compressors are packed individually in a cardboard box. They can be ordered in any quantity. Minimum ordering quantity = 1. As far as possible, Danfoss will ship the boxes on full pallets of 6 or 9 compressors according below table.
Application Guidelines Ordering information and packaging Single pack Brazed version Model Voltage Voltage Voltage Voltage Voltage Voltage Compressors Connections Features variation code 1 code 2 code 4 code 5 code 7 code 9 MLZ015 120U8036 121U8002 121U8024 MLZ019 121U8060 121U8038 121U8004 121U8026 MLZ021...
Application Guidelines Ordering information and packaging Industrial pack Brazed version Model Voltage Voltage Voltage Voltage Voltage Voltage Compressors Connections Features variation code 1 code 2 code 4 code 5 code 7 code 9 MLZ015 120U8035 121U8001 121U8023 MLZ019 121U8059 121U8037 121U8003 121U8025 MLZ021...
Application guidelines Danfoss scroll compression principle In a Danfoss SM / SY / SZ scroll compressor, the compression is performed by two scroll elements located in the upper part of the compressor. Suction gas enters the compressor at the suction connection.
Page 135
In addition to the existing SM range compressors Part protection and assembly reduces internal leaks and increases life durability. previously available, Danfoss is completing its range with 3 compressors. Improved part isolation reduces greatly acoustic The new SM112-124-147 and SZ147 compressors levels.
"Ordering information & packaging". units. The example below presents the single compressor nomenclature which equals the For tandem and trio assemblies, please refer technical reference as shown on the compressor to the Danfoss Parallel Application Guidelines nameplate. documentation FRCC.PC.005. Nomenclature Family, lubricant...
Displacement at nominal speed: 2900 rpm at 50 Hz, 3500 rpm at 60Hz Net weight with oil charge Data given for code 4 compressor, for full data details and capacity tables refer to Online Datasheet Generator: www.danfoss.com/ODSG Rating conditions...
Displacement at nominal speed: 2900 rpm at 50 Hz, 3500 rpm at 60Hz Net weight with oil charge Data given for code 4 compressor, for full data details and capacity tables refer to Online Datasheet Generator: www.danfoss.com/ODSG Rating conditions...
2’’ 1/8 SY/SZ 380 Discharge 1’’ 3/8 All Danfoss SM / SY / SZ scroll compressors come Oil sight glass equipped with a sight glass (1"1/8-18 UNF) which may be used to determine the amount and condition of the oil contained within the sump.
Application guidelines Electrical data, connections and wiring Motor voltage Danfoss SM / SY / SZ scroll compressors are available in five different motor voltages. Motor voltage Motor voltage Motor voltage Motor voltage code 3 code 4 code 7 code 9...
Application guidelines Electrical data, connections and wiring The terminal box is provided with 2 double SM/SZ 175-185 - J, K, P, S, U, W, Cover holding screw (x2) - Torque: 1.6 ft.lb X, Y versions knockouts for the power supply and 3 knockouts Terminal box for the safety control circuit.
158°F. Consequently, if the compressor is installed in an enclosure, precautions must be will not be covered by Danfoss warranty. In the taken to avoid that the temperature around the same manner, cables must be selected in a way...
Page 148
77°F, the measured resistance must be corrected with following formula: Danfoss MCI soft-start The inrush current for the Danfoss scroll effects of high starting torque surges and costly controller compressors with motor code 4 (400V / 3 / 50Hz...
Application guidelines Electrical data, connections and wiring When the control voltage is applied to A1 - Input controlled soft start A2, the MCI soft starter will start the motor, according to the settings of the ramp-up time and initial torque adjustments. When the control voltage is switched OFF, the motor will switch off instantaneously.
Application guidelines Electrical data, connections and wiring Compressor models SM / SZ 175 – 185 R and C version CONTROL CIRCUIT CONTROL CIRCUIT 180s 180s LLSV Wiring diagram without pump-down cycle Wiring diagram with pump-down cycle Compressor models SM/SZ175-185 (J, K, P, S, U, W, X, Y versions) Wiring diagram without pump-down cycle Wiring diagram with pump-down cycle Compressor models SY / SZ 240 - 300 - 380...
Page 151
Application guidelines Electrical data, connections and wiring Motor protection The table below shows the protection method for the various compressors models. Overheating protection Over current protection Locked rotor protection Phase reversal protection SM/SZ 115-125-160-175-185 Internal thermostat External overload protection Reverse vent.
Page 152
Application guidelines Electrical data, connections and wiring If any thermistor exceeds its response A red/green twin LED is visible on the module. temperature, its resistance increases above A solid green LED denotes a fault free condition. A blinking red LED indicates an identifiable fault the trip level (4,500 Ω) and the output relay then trips -ie.
Application guidelines Electrical data, connections and wiring The lockout may be cancelled by resetting the Compressor power mains (disconnect L-N) for approximately start 5 sec. Phase monitoring Phase sequence module logic Voltage unbalance The operating voltage limits are shown in the voltage unbalance is 2%.
SM / SY / SZ models (European Directive) SM / SY / SZ All 60 Hz models (Underwriters Laboratories) Other approvals / certificates Contact Danfoss Pressure Equipment Products SM084 to 185 SZ084 to 185 & SY185 SY/SZ 240 to 380 Directive 97/23/EC Refrigerating fluids...
Application guidelines Operating conditions • Refrigerant and lubricants The scroll compressor application range is • Motor supply influenced by several parameters which need to • Compressor ambient temperature be monitored for a safe and reliable operation. These parameters and the main Application envelope (evaporating temperature, recommendations for good practice and safety condensing temperature, return gas...
Application guidelines Operating conditions Motor supply SM / SY / SZ scroll compressors can be operated allowed within the indicated voltage ranges. In at nominal voltages as indicated on page 18. case of risk of under-voltage operation, special attention must be paid to current draw. Under-voltage and over-voltage operation is Compressor ambient SM / SY / SZ compressors can be applied from...
When discussing DEW point temperatures. In these Selection and evaporating and condensing temperatures Application Guidelines, Danfoss Commercial Compressors displays temperatures as DEW therefore, it is important to indicate whether these are DEW point values or MEAN point point values.
Page 159
Application guidelines Operating conditions Dew temperature and mean temperature for R407C pressure (log) Mean Mean enthalpy The following operating diagrams show the difference between mean and dew temperature application envelopes. Dew temperature conditions Dew temperature Example for SZ 084 to 185 S.H.
Application guidelines Operating conditions Discharge temperature The discharge gas temperature must not exceed discharge temperature must be monitored protection 275°F. The discharge gas thermostat accessory kit during development test by the equipment manufacturer. (code 7750009) includes all components required for installation, as shown below. The thermostat must be attached to the discharge line within The DGT should be set to open at a discharge gas 150 mm from the compressor discharge port and...
13 psi for R22. The compressor can be operated situations, for example 7 psi for R22. Cycle rate limit Danfoss recommends a restart delay timer to necessary, place an anti-short-cycle timer in the limit compressor cycling. The timer prevents control circuit, connected as shown in the wiring reverse compressor rotation, which may occur diagram section "Suggested wiring diagrams...
Application guidelines System design recommendations General Successful application of scroll compressors beyond the limits given in this manual. Poor is dependent on careful selection of the performance, reduced reliability, or both may result. compressor for the application. If the compressor is not correct for the system, it will operate Essential piping design Proper piping practices should be employed to...
Note: for special conditions such as low ambient temperature, low refrigerant load or brazed plate heat exchangers please refer to corresponding section "Specific application recommendations". More detailed information can be found in the paragraphs hereafter. Please contact Danfoss Technical Support for any deviation from these guidelines.
Page 164
Sump heater accessories are available from charge for compressors requires a crankcase Danfoss (see section "Accessories"). An LLSV may be used to isolate the liquid charge The quantity of refrigerant on the low pressure...
A continuous liquid flood back will cause oil dilution and, in extreme situations lead to lack Danfoss SM/SY/SZ scroll compressors can of lubrication and high rate of oil leaving the tolerate occasional liquid flood back. However compressor.
"High and low pressure The Danfoss SM/SY/SZ scroll compressor requires levels during low loading periods. A minimum of Low ambient operations a minimum pressure differential of 87 to 102 psi 9 °F stable superheat is required.
Application guidelines Specific application recommendations Sump heaters are strongly recommended on will minimize refrigerant migration caused by Sump heaters the large temperature gradient between the all systems where the compressor is exposed to low ambient temperatures, especially split and compressor and the remainder of the system, remote condenser installations.
Page 168
275°F. The Danfoss SM/SY/SZ scroll compressor is a high position. At the same time, it is important that Discharge line...
Application guidelines Specific application recommendations The use of a suction line accumulator is strongly the cycle switches back to a defrost cycle or to Suction line accumulator normal cooling operations. recommended in reversible cycle applications as a result of the possibility of a substantial quantity of liquid refrigerant remaining in the evaporator, Sustained and repeated liquid slugging and which acts as a condenser during the heating...
* Bottom insulations are provided in surface sump heater accessories. Materials are UL approved and RoHS compliant. Data given for code 4 compressor, for full data details and capacity tables refer to Online Datasheet Generator: www.danfoss.com/ODSG Stopping sound level SM / SY / SZ compressors are equipped with a...
Page 171
Because of the Danfoss’s unique design of a full-suction gas-cooled motor, compressor body The Danfoss SM / SY / SZ scroll compressor is insulation across its entire operating range is designed to be quiet and the frequency of the possible.
Compressor handling and Each Danfoss SM / SY / SZ scroll compressor is and between -31°F and 158°F when charged with storage equipped with two lift rings on the top shell.
Nut * in place before shipping the unit with the * not supplied with compressor compressor installed. Note: for parallel assemblies see specific recommendations in Danfoss parallel application guidelines", FRCC.PC.005. Compressor holding charge Each compressor is shipped with a nominal dry plug first and the discharge plug afterwards.
Page 174
For specific temperature has been reached there as well, and applications not covered herein, please contact Danfoss Commercial Compressors for further then begin adding the brazing material. Move the torch evenly around the joint, in applying information.
Application guidelines Installation System pressure test Always use an inert gas such as nitrogen for an inflammable mixture. Do not exceed the pressure testing. Never use other gasses such as following pressures: oxygen, dry air or acetylene as these may form Maximum compressor test pressure (low side) SM/SZ 084 - 185: 363 psig SZ/SY240 - 380: 290 psig...
50 ppm end point dryness (EPD). After burn out, remove & replace the liquid line filter drier and install a Danfoss type DAS burn- For new installations with SM/SY/SZ compressors out drier of the appropriate capacity. Refer to the...
Danfoss scroll compressors may be ordered following tables For tandem assemblies, please from Danfoss Commercial Compressors in either refer to the Danfoss parallel application guideline industrial packs or in single packs as listed in reference FRCC.PC.005. SM112-124-147 compressors in industrial pack Code no.
Page 179
Application guidelines Ordering information & packaging SM /SY compressors in single pack Code no. Compressor Motor Connections model protection 460/3/60 575/3/60 200-230/3/60 380/3/60 380-400/3/50 500/3/50 SM084 Brazed Internal SM084-3VI SM084-4VI SM084-7VI SM084-9VI SM090 Brazed Internal SM090-3VI SM090-4VI SM090-7VI SM090-9VI SM100 Brazed Internal SM100-3VI...
Page 180
Application guidelines Ordering information & packaging SZ compressors in single pack R407C / R134a Code no. Compressor Motor Connections model protection 460/3/60 575/3/60 200-230/3/60 380/3/60 380-400/3/50 500/3/50 SZ084 Brazed Internal SZ084-3VI SZ084-4VI SZ084-7VI SZ084-9VI SZ090 Brazed Internal SZ090-3VI SZ090-4VI SZ090-7VI SZ090-9VI SZ100 Brazed...
Page 181
Application guidelines Accessories Solder sleeve adaptator set Pack Type Code n° Description Application Packaging size 7765005 Solder sleeve adapter set (1"3/4~1"1/8), (1"1/4~3/4") SM/SZ084-090-100 Multipack SM110-112-120-124-147-148-161& 120Z0405 Solder sleeve adapter set (1"3/4~1"3/8), (1"1/4~7/8") Multipack SZ110-115-120-125-147-148-161 SM110-112-120-124-147-148-161& 7765006* Solder sleeve adapter set (1"3/4~1"3/8), (1"1/4~7/8") Multipack SZ110-115-120-125-147-148-161 7765028 Solder sleeve adapter set (2"1/4~1"5/8), (1"3/4~1"1/8)
Application guidelines Accessories Rotolock nuts Pack Type Code n° Description Application Packaging size 8153123 Rotolock nut,1"1/4 Models with 1"1/4 rotolock connection Multipack 7953002 Rotolock nut,1"1/4 Models with 1"1/4 rotolock connection Industry pack 8153124 Rotolock nut,1"3/4 Models with 1"3/4 rotolock connection Multipack 7953003 Rotolock nut,1"3/4 Models with 1"3/4 rotolock connection...
Page 183
Application guidelines Accessories Discharge temperature protection Pack Type Code No Description Application Packaging Size 7750009 Discharge thermostat kit All models Multipack 7973008 Discharge thermostat kit All models Industry pack Mounting hardware Pack Type Code No Description Application Packaging Size Mounting kit for scroll compressors. Grommets, SM/SZ084-090-100-110-120-148-161-175- 8156138 Single pack...
Page 184
Sight glass with gaskets (black & white) All models Multipack 8156129 Gasket for sight glasse, 1"1/8 (white teflon) All models Multipack 7956005 Gasket for sight glass, 1"1/8 (white teflon) All models Multipack 8154001 Danfoss Commercial Compressors blue spray paint All models Single pack FRCC.PC.003.A5.22...
Page 186
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.